2.7 Functional
check
Connections must be tested if all settings were made to the web server as well as
to system devices.
Test condition
A PC on the local network is used to test operations via LAN. The login dialog box
must appear after entering the local IP address for the web server (see Section
2.2.2).
LAN
We recommend using mobile participants with Internet access (Smartphone,
mobile phone) to test operation over the Internet. The login dialog box must appear
after entering the public IP address or plant domain (see Section 3).
Internet
A text message with plant status is received after a text message (possibly with
assword) is sent to the plant's phone number (see Section
SMS operation
p
Example
1. Create text message:
– Password required: *<Password> #
– No password required: #
2. Send message plant phone number.
Do the test if the web server is to send a message or system report via e-mail or
SMS for a fault.
Test message receiver
The test is also carried out if message suppression is switched on.
Note
Path: Home > 0.5 OZS164… > Settings > Message receiver
Data point
Explanation, example
T
est message receiver
Default val.:
---
Setting val:
Message receiver 1..4
Select a message recipient to test the
connection to it.
—
S
ystem report sent
Display values: ---, Yes, No
The display after a few seconds from "
---
" to:
Yes
: Message sent successfully.
o
:
Message recipient not reached.
N
—
M
essage inhibition
Display values: Yes, no
Shows the message suppression switch
etting (
8
) (see Section
s
1.2).
—
43 / 108
Siemens Web
server
CE1C5711en
Building Technologies
Commissioning
25.08.2010