5 / 10
A6V10636202_enAP_c
Siemens
2018-01-25
Building Technologies
Inputs
Positioning signal for GLB14..1E
Operating voltage AC/DC 24 V
AC 24 V ~ / DC 24…48 V
⎓
(wires 1-6/G-Y1)
(wires 1-7/G-Y2)
clockwise
counterclockwise
Positioning signal for GLB34..1E
Operating
voltage
AC 100…240 V ~
(wires 4-6/N-Y1)
(wires 4-7/N-Y2)
clockwise
counterclockwise
Positioning signal for GLB16..1.E
Input
voltage
Current
consumption
Input
resistance
(wires 8-2/Y-G0)
DC 0/2…10 V
⎓
0.1 mA
>100 k
W
Max. permissible input voltage
Protected against faulty wiring
DC 35 V
⎓
limited to DC 10 V
⎓
max. AC 24 V ~ / DC 24…48 V
⎓
Hysteresis
for non-adjustable characteristic function
for adjustable characteristic function
60 mV
0.6 % of ∆U
Adjustable characteristic function (GLB163.1E, GLB164.1E)
Adjustable with 2 potentiometers:
Max. input voltage
Protected against faulty wiring
Offset Uo
Span ∆U
DC 0…5 V
⎓
DC 2…30 V
⎓
DC 35 V
⎓
max. AC 24 V ~ / DC 24…48 V
⎓
Outputs
Position indicator
Output signal (GLB16..1E)
Output signal (GLB36..1E)
Output voltage U
Max. output current
(wires 9-2/U-G0)
(wires 9-2/U-G-)
DC 0...10 V
⎓
DC ±1 mA
Protected against faulty wiring
max. AC 24 V ~ / DC 24…48 V
⎓
Aux. power supply (G- / G+)
GLB36..
DC 24 V
⎓
±20 %, max. 10 mA
Feedback potentiometer (for GLB142.1E)
Change of resistance
(wires P1-P2)
0…5000
W
Load
Max. sliding contact current
Permissible voltage at potentiometer (SELV/PELV)
Insulation resistance between potentiometer and
housing
<0.25 W
<10 mA
AC 24 V ~ / DC 24…48 V
⎓
AC 500 V ~
Auxiliary switches (GLB146.1E, GLB166.1E, GLB346.1E)
Switching voltage
Contact rating
Electric strength auxiliary switch against housing
Switching range for auxiliary switches / setting increments
AC 24…250 V ~ / DC 12…30 V
⎓
6 A resistive, 2 A inductive, min. 10 mA @ AC
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V
⎓
0.8 A res., 0.5 A inductive, min. 10 mA @ DC 60 V
⎓
AC 4 kV
5°…90° / 5°
Factory switch setting:
Switch A
Switch B
5°
85°
Connection cables
Cable length
0.9 m
Cross section of prewired connection cables
0.75 mm
2
Permissible length for signal lines
300 m
Degree of protection
Insulation class
AC 24 V ~ / DC 24…48 V
⎓
, feedback potentiometer
AC 100…240 V ~, auxiliary switches
As per EN 60730
III
II
Housing protection
IP 54 as per EN 60529