Technical Instructions
GBB/GIB Series Non-spring Return, 24 Vac, Modulating Control
Document Number 155-176P25
June 22, 2015
Page 12
Siemens Industry, Inc.
Mechanical Range
Adjustment,
Continued
3. Return the actuator gear train to the "0" position using the steps that follow for the
clockwise or counterclockwise damper shaft rotation.
Clockwise-to-open:
a. Insert the shaft adapter to the right as close as possible to the raised stop. See
b. Hold down the
PUSH
button and rotate the shaft adapter to the left until it stops.
c. Release the
PUSH
button.
d. If the shaft adapter is not resting against the left raised stop, remove the adapter
and insert it against the left stop.
e. Place the position indicator to the "0" position on the outside scale.
Counterclockwise-to-open:
a. Insert the shaft adapter to the left as close as possible to the raised stop.
b. Hold down the
PUSH
button and rotate the shaft adapter to the right until it stops.
c. Release the
PUSH
button.
d. If the shaft adapter is not resting against the right raised stop, remove the adapter
and insert it against the right stop.
e. Place the position indicator to "0" on the inside scale.
4. Determine the angle of rotation for the damper blade shaft. Subtract that amount from 90°.
5. Remove the shaft adapter and insert it with the position indicator pointing to mark on the
scale calculated in the previous step. See Figure 26.
6. Attach the clip.
7. Rotate the damper blade shaft to its "0" position.
8. Return the actuator to the damper shaft and tighten the shaft adapter to the damper shaft.
Figure 26. Mechanical Range Adjustment.