B-12
Equipment Manual OP7, OP17
Release 04/99
Remedy:
Cause
Mes-
sage
632
Configuration error:
Variable x:
1, 4
Information text does not exist
2
Information text ID for messages does not exist
3, 6..8, Internal error
11, 13
5
Field only created symbolically.
9
Screen or recipe entry created symbolically only
12
Process screen or recipe does not contain any en-
tries
Check the configuration.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
634
Configuration error:
Variable x:
0..8, 34 Internal error
18
Screen or recipe title not configured
Screen or recipe title not configured
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
635
Configuration error:
Variable x:
1
Screen or recipe entry created symbolically only
3
Field only created symbolically.
6
Message, entry or information text not configured
for current language
7...9,
Internal error
19, 28,
41...43
18
Screen or recipe title not configured
20
Process link only created symbolically.
21
Information text only created symbolically.
22
Symbolic field only created symbolically.
23
Fewer than 2 field texts configured for symbolic
field
24
Current field type for symbolic field not configu-
red
25
Illegal data format for symbolic field (only KF
and KY permissible)
26
Recipe setpoint configured with data format KC
33
Illegal data format for setpoint field
35
Data format for scheduler too short
36
Illegal data format for actual control value
44
With a permanently programmed Return to
menu: menu item not present
45
With permanently programmed Return to screen:
entry or field number not present
46
Too many control actual values on screen (no
more than 200 allowed)
48
Too many fields on process screen
50
Process link for soft keys does not exist
51
Soft key number too high
53
Information text for soft key not configured or
not configured in all languages
55
Soft key specified in entry does not exist
Check the configuration.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
636
Event message is not configured
Configure event message (–> message
number) fully.
Содержание OP17
Страница 8: ...iv Equipment Manual OP7 OP17 Release 04 99 Preface ...
Страница 13: ...Product Description 1 Functionality 2 Part I Introduction ...
Страница 14: ...2 2 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 24: ...1 10 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 28: ...2 4 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 30: ...2 6 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 76: ...7 16 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 92: ...9 6 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 98: ...10 6 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 100: ...10 8 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 106: ...11 6 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 111: ...Installation 14 Commissioning 15 Device Description 16 Part IV Commissioning and Description of Devices ...
Страница 112: ...13 4 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 140: ...16 10 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 142: ...P 12 Equipment Manual OP7 OP17 Release 04 99 ...
Страница 164: ...B 20 Equipment Manual OP7 OP17 Release 04 99 ...