background image

GAMMA

instabus

Technical Product Information

March 2014

IP Router N146/02

5WG1 146-1AB02

Siemens AG

N 146/02, 8 pages

Technical Manual

Infrastructure & Cities Sector, Building Technologies
Control Products and Systems

ã

 Siemens AG 2014

Update: http://www.siemens.com

P.O.Box 10 09 53, D-93009 Regensburg

Subject to change without prior notice

2.11.1.13/5

Power supply

·

  Bus voltage: via KNX/EIB bus line

·

 Operating voltage:

from “Power over Ethernet” according to IEEE 802.3af,
nominal voltage DC 48V
alternatively, from external SELV power supply AC/DC
24V nominal,
permissible input voltage range:
AC 12...24V, DC 12 ... 30 V

·

 Recommended power supplies:

DC 29V (before choke) from KNX/EIB power supply
N125/21

Power supply unit 4AC2 402
Primary voltage AC 85-265V / DC 85-300V,
Secondary voltage DC 24V, 2MU width

safety transformers 4AC3 724-0
Primary voltage 230V AC Secondary voltage AC 12V,
3MU width
safety transformers 4AC3 740-1
Primary voltage 230V AC Secondary voltage AC 12V
24V, 5MU width

V

CAUTION

It is recommended to use the external safety extra low
voltage power supply for the IP Router N146/02 only.

Power usage

·

  From the bus line: max. 10mA @ DC 29V

·

  From the auxiliary power supply: max. 1,7 W

(57mA @ DC 24V)

Control elements

1 learning button:
for switching between normal operating mode and
addressing mode

Display elements

·

  1 green LED: device ready (ON)

·

  1 yellow LED: Communication on bus line

·

  1 green LED: Ethernet Link Signal available (Lk)

·

  1 yellow LED: Receiving data from Ethernet (Rx)

·

  1 red LED: Transmitting data to Ethernet (Tx)

·

  1 red LED: for monitoring bus voltage and displaying

mode, selected with the learning button

Connections

·

  bus line: screwless bus connection block (red-black)

0,6...0,8 mm Ø single core
remove approx. 5mm of isolation

·

  Ethernet / IP network: RJ45 socket

·

 auxiliary power:

screwless extra low voltage terminal (yellow-white)

Æ

 0,6 ... 0,8 mm Ø single core

remove approx. 5mm of isolation

Physical specifications

·

 housing: plastic

·

  N-system DIN-rail mounted device,

width: 2 SUs (1SU = 18mm)

·

Installation: Snap-on mounting on DIN rail
EN 60715-TH35-7.50

·

  weight: approx. 105g

·

Fire load: approx. 2840 kJ

±

 10 %

Electrical safety

·

  degree of pollution (according to IEC 60664-1): 2

·

  protection (according to EN 60529): IP 20

·

  protection class (according to IEC 61140): III

·

  overvoltage class (according to IEC 60664-1): III

·

  bus: safety extra low voltage SELV DC 24 V

·

  the device complies with EN 50 090-2-2

Electromagnetic compatibility

complies with
EN 61000-6-2 and EN 61000-6-3 and EN 50090-2-2

Environmental specifications

·

  climatic conditions: EN 50090-2-2

·

  ambient temperature operating: - 5 ... + 45

°

C

·

  storage temperature: - 25 ... + 70

°

 C

·

  relative humidity (non-condensing): 5 % to 93 %

Markings

KNX, EIB, CE

CE mark

complies with the EMC regulations (residential and
functional buildings), and low voltage regulations

Содержание N146/02

Страница 1: ...rarchically superimposed systems via Internet Protocol IP Direct access to the KNX EIB installation from any access point to the IP network KNXnet IP Tunneling Fast communication between KNX EIB lines areas and systems KNXnet IP Routing Communication between buildings and facilities Filtering and routing of telegrams depending on individual address group address LED display of operation KNX EIB co...

Страница 2: ... 5 5 1 Figure 1 IP Router as area and line coupler EIBnet IP Router 1 0 0 IP Network EIBnet IP Router 2 0 0 Main Line 1 Main Line 2 Line Coupler 1 1 0 Line Coupler 1 2 0 Line Coupler 1 3 0 Line Coupler 2 1 0 Line Coupler 2 2 0 Device 1 1 1 Device 1 1 2 Device 1 2 1 Device 1 2 2 Device 1 3 1 Device 1 3 2 Device 2 1 1 Device 2 1 2 Device 2 2 1 Device 2 2 2 4 1 1 4 1 1 4 1 1 5 2 1 5 2 1 4 1 1 4 1 1 4...

Страница 3: ...e one or more of the additional individual addresses could be assigned twice When during normal operation the learning button is pressed for more than 10 seconds all additional individual addresses in the IP Router N146 02 are reset to the default value 15 15 255 and the programming LED is turned off IP address assignment The IP address of the IP Router N146 02 is assigned manually using ETS autom...

Страница 4: ...ay be used for permanent interior installations in dry locations within distribution boards or small casings with DIN rail EN 60715 TH35 7 5 V WARNING The device must be mounted and commissioned by an authorised electrician Free DIN rail areas with sticked in data rails must be covered with covers order no 5WG1 192 8AA01 The prevailing safety rules must be heeded The device must not be opened For ...

Страница 5: ...nd addressing mode Display elements 1 green LED device ready ON 1 yellow LED Communication on bus line 1 green LED Ethernet Link Signal available Lk 1 yellow LED Receiving data from Ethernet Rx 1 red LED Transmitting data to Ethernet Tx 1 red LED for monitoring bus voltage and displaying mode selected with the learning button Connections bus line screwless bus connection block red black 0 6 0 8 mm...

Страница 6: ...iption The N system DIN rail device can be installed in N system distribution boards surface or flush mounted or on any DIN rail complying with EN 60715 TH35 7 5 The connection to the bus line is established via the bus connector terminal red black on the top side The RJ45 socket on the device front side provides the connection to the Ethernet IP data network Mounting DIN rail devices Figure 5 Sli...

Страница 7: ...single core conductors Ø 0 6 0 8 mm Remove approx 5 mm of insulation from the conductor D2 4 and plug it into the bus connection block D2 red black Disconnecting bus cables Figure 6 Unplug the bus connection block E1 and remove the bus cable conductor E1 4 while simultaneously wiggling it D2 D D2 D2 4 5 mm D2 D2 4 D2 1 D2 2 D2 D2 3 Figure 6 Connecting and disconnecting bus wires Slipping off on au...

Страница 8: ... net works ETS 3 0c or higher An KNXnet IP driver is available for ETS3 When this driver is installed ETS3 may use the IP Interface N148 21 the IP Router N146 the IP Controller N350E and the IP Viewer N151 as interfaces to the bus just like a standard RS232 or USB serial interface This function includes download of device configuration via the bus and the group monitor function of ETS3 Note The KN...