Performing a firmware update on 

MultiRanger 200 HMI 

Application examples 

 

 

09\2020 

AG061215 

Introduction 

 

 

Procedure 

 

 

 

 

 

 

Содержание MultiRanger 200 HMI

Страница 1: ...Performing a firmware update on MultiRanger 200 HMI Application examples 09 2020 AG061215 Introduction 1 Procedure 2 ...

Страница 2: ...ated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Sieme...

Страница 3: ...ming a firmware update on MultiRanger 200 HMI Application examples 09 2020 AG061215 3 Table of contents 1 Introduction 4 1 1 Objective 4 1 2 Equipment 4 1 3 Disclaimer 4 2 Procedure 5 2 1 Updating Firmware 5 ...

Страница 4: ...iRanger 200 HMI 1 2 Equipment Equipment Article No MultiRanger 200 HMI 7ML5033 Dolphin cable adapter DB 9 to RJ 11 2 1b telephone cable 7ML1830 MC RJ 11 telephone cable A PC with a RS 232 serial port USB to RS 232 adapters work too Administrator rights on your PC The firmware image in BS2 format A downloader 1 3 Disclaimer Note While every effort is made to verify the following information no warr...

Страница 5: ...B converter 4 Connect MultiRanger 200 HMI to the power source 5 Ensure the communication parameters are set as follows Parameter Setting Parameter description 4 1 Communications Port Se lector 1 RS 232 port RJ 11 modular telephone Sets the communications port index for all parameters appli cable to this sub menu 4 2 Device Address 2 Sets the unique identifier of the MultiRanger on the network 4 4 ...

Страница 6: ...ill then see the communications options dialog box Please choose the following options Set slave address to 1 for sensor board or 2 for HMI Set the com port to PC Set the baud rate to 115200 Set other communications to 8 data bits no parity and 1 stop bit 9 Click Next 10 Click Start to begin the download 11 Once the download is complete the following window will appear Click OK ...