Document No. 565-887

Installation Instructions

October 27, 2006

FLN

DRIVER

TX-

TX+

RX-

RX+

RX-

RX+

TX-

TX+

S

-

+

RS-485 TRUNK CABLE

 (MAX 4000’ / 1219.2 m;

 STANDARD 24 AWG LOW CAPACITANCE)

GROUND WIRE TO EARTH

(P/N 538-583)

POWER PACK

TRUNK / RS-422

INTERFACE

MODBUS

DEVICE(S)

GW0277R3

TAPE BACK

SHIELD

ONE TWISTED PAIR

 (STANDARD 24 AWG LOW CAPACITANCE)

MAX LENGTH  4000’

TO ADDITIONAL MODBUS DEVICES

POWER

TERMINAL

BLOCK

TERMINAL

BLOCK

PMD

S

-

+

Figure 1.

Using a Trunk/RS-422 Interface to Connect the Driver to the Vendor’s Modbus Master or Modbus Slave

Device.

Siemens Building Technologies, Inc.

Page 3 of 6

Содержание Modbus Driver

Страница 1: ...DI 8DO 8AI 8AO point expansion support modem with HOA 986 90392G Modbus Driver MEC with Ethernet ALN 8DI 8DO 8AI 8AO point expansion support HOA ready 986 90392H Modbus Driver MEC with Ethernet ALN 8DI 8DO 8AI 8AO point expansion support with HOA 986 90392L Modbus Driver MEC with BACnet IP ALN 8DI 8DO 8AI 8AO point expansion support HOA ready 986 90392M Modbus Driver MEC with BACnet IP ALN 8DI 8DO...

Страница 2: ...ting the Driver to the Vendor s Modbus Master or Modbus Slave Device section CAUTION Always wear an electro static discharge wrist strap and discharge accumulated static before touching field panel components Prerequisites Driver hardware is installed according to its respective installation instructions FLN Termination blocks installed if any One AC power receptacle for each communication interfa...

Страница 3: ...TH P N 538 583 POWER PACK TRUNK RS 422 INTERFACE MODBUS DEVICE S GW0277R3 TAPE BACK SHIELD ONE TWISTED PAIR STANDARD 24 AWG LOW CAPACITANCE MAX LENGTH 4000 TO ADDITIONAL MODBUS DEVICES POWER TERMINAL BLOCK TERMINAL BLOCK PMD S Figure 1 Using a Trunk RS 422 Interface to Connect the Driver to the Vendor s Modbus Master or Modbus Slave Device Siemens Building Technologies Inc Page 3 of 6 ...

Страница 4: ...INTERFACE II MODBUS DEVICE S GW0295R2 TAPE BACK SHIELD 3 CONDUCTOR MAX 50 15 24 m STANDARD 24 AWG LOW CAPACITANCE POWER RS 232 PORT 25 PIN FEMALE PMD S IF DRIVER IS LESS THAN 50 CABLE FEET 15 24 m FROM MODBUS DEVICE PLACE TRUNK INTERFACE II IN MBC ENCLOSURE Figure 2 Using a Trunk Interface II to Connect the Driver to the Vendor s Modbus Master or Modbus Slave Device Page 4 of 6 Siemens Building Te...

Страница 5: ...AX 4000 1219 2 m STANDARD 24 AWG LOW CAPACITANCE ONE TWISTED PAIR MODBUS DEVICE S GW1042R2 TAPE BACK SHIELD TO ADDITIONAL MODBUS DEVICES TERMINAL BLOCK IF APPLICABLE Figure 3 Direct Connect the Driver to the Vendor s Modbus Master or Modbus Slave Device Siemens Building Technologies Inc Page 5 of 6 ...

Страница 6: ...ents are introduced Product or company names mentioned herein may be the trademarks of their respective owners 2006 Siemens Building Technologies Inc Siemens Building Technologies Inc Your feedback is important to us If you have Document No 565 887 1000 Deerfield Parkway comments about this document please send Country of Origin US Buffalo Grove IL 60089 4513 them to SBT_technical editor siemens c...

Отзывы: