
Siemens Industry, Inc.
Building Technologies Division
A6V10328217_en--_f
3
PRE-INSTALLATION
The following components must be set prior to inserting the card into the CC-5/CC-2
(refer to Figure 2):
The MLC uses two module addresses in the HNET network. Set the lower of the
two consecutive three-digit HNET network addresses (odd or even) for the MLC
using the three rotary dial switches located near the bottom of the front panel. (Refer
to Figure 1 for the location of the switches.) The address for the MLC must be the
same as the address selected for it in the Zeus Programming Tool. To set the address,
turn the pointers on each of the three dials to the numbers for the selected address.
For example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set
the pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”. The
range of allowable addresses is from 001 to 251 (leading zeros must be used).
INSTALLATION
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
The MLC plugs perpendicularly into one slot in the CC-5/CC-2 card-cage via two 96-
pin DIN connectors and can occupy any slot in the card cage. (Refer to Figure 2.)
Insert the MLC card into the card guides rightside up (lettering on the front panel is
legible).
Slide the card in until the card edge connectors contact the
receptacles on the motherboard.
Verify that the DIN connectors of the card and the card-cage
aligned properly. The card can only plug in one direction to the
card cage, if it does not align, DO NOT FORCE the card.
Place thumbs on the front panel adjacent to the captive
screws and gently apply even pressure on the card until the
connectors seat in the receptacles on the motherboard.
Secure with the captive screws.
FIRMWARE UPGRADES
The MLC is shipped with the latest firmware and the user should not have to
upgrade unless suggested to do so by Siemens Industry, Inc. Technical Support.
From time to time, modules used in XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular systems are upgraded to improve their operation or to add to their capabili-
ties with new features. Firmware in the MLC is field upgradable. Refer to the Zeus
Quickstart Manual, P/N 315-033875, and Zeus Help for additional details.
1.
Plug one end of a user-supplied USB A to B cable into the USB port on the
front of the MLC. Plug the other end into the host PC.
2.
In Zeus, select the module to be upgraded in the Physical Tree. Then select
the
Build>Transfer>Module Firmware to Panel
menu.
HNET
HUNDREDS
TENS
ONES
Figure 2
Installing The MLC