![Siemens MJ-4A Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/siemens/mj-4a/mj-4a_installation-manual_376318038.webp)
34
84
SF = 1
Memo2 - chars 9-10
85
SF = 1
"NN" Raise/Lower Value
86
SF = 1
Regulator Id (Range: 0 - 32766)
87
SF = 1
Tap Changer Mechanism
88
SF = 1
Max. Load Current % (Range: 0-350)
89
SF = 1
Full Load Current (50-7200) (A)
90
SF = 1
CM Pre-tx delay for DNP
91
SF = 1
CM Post-tx delay for DNP
92
SF = 1
CM transmit delay for DNP
93
SF = 1
CM number of retries (DNP)
94
SF = 1
CM protocol
95
SF = 1
CM parity
96
SF = 1
CM self test request
97
SF = 1
Raise Limit % (0=10%, 1=8.75%, 2=7.5%, 3=6.25%, 4=5%)
98
SF = 1
Lower Limit % (0=10%, 1=8.75%, 2=7.5%, 3=6.25%, 4=5%)
99
SF = 1
Data Port Baud
9 Communications Module Firmware Versions
9.1 MJ-4 Communications Module firmware version
Version 3.10 : Supports all DNP points including Set 7, supports AMD Flash memory.
9.2 MJ-XL Communications Module firmware versions
The principle firmware version released for the MJ-4 Communications Module is the 3.10, an abbreviated list of the
principle firmware versions that have were released for use on the MJ-X
L
communications module follows. For
questions regarding firmware versions not included in this list, please contact your Siemens representative.
Version 2.13: Contains “full set” of 370 DNP3.0 points (see 2.x3 points list in Section 8.2.9).
Version 2.14: Contains “limited set” of 64 DNP3.0 points (see 2.x4 points list in Section 8.2.3).
Version 3.01: Level 2 implementation of DNP3.0, no DNP points by default; must use the DNP Configure program
to load the desired DNP points onto the control panel. Supports unsolicited responses.
Version 3.07: Level 2 implementation of DNP3.0, can use DNP Configure program to load user-defined DNP points
or choose to use one of the predefined DNP point sets (if used in conjunction with MJXL version 3.07
or higher).
Version 3.0701: Added short delay after CM initialization so all values are online before polling can start
Version 3.0702: Added full support for Trip/Close operations on Binary Outputs. If using a Trip/Close operation for
a tap raise or lower, the TRIP command should be used to activate. Also, a
Trip
to the Tap Raise
point will
raise
the tap one position; a
Close
to the Tap Raise point will
lower
the tap one position.
Version 3.0703: Added support for alternate AMD flash memory. Removed support for ATMEL Flash memory.