28
10
SF = 1
VRC1 contacts
11
SF = 1
VRC2 contacts
12
SF = 1
Remote Switch position
13
SF = 1
Manual Switch position
14
SF = 1
Auto Inhibit Out Status
Binary Outputs
Point #
Scale Factor
Description
0
SF = 1
Tap Raise
1
SF = 1
Tap Lower
2
SF = 1
Auto Inhibit (Latch On/Off)
Analog Inputs
Point #
Scale Factor
Description
0
Op Count Last Year
1
N/A
2
SF = 1
R/A/M switch position
3
Power Flow Direction Indicator
4
SF = 1
VRC contacts status
5
SF = 1
Band, VRC, VLC status
6
SF = 1
Tap Position
7
SF = 1
Load Current
8
SF= 10
Load Voltage
9
SF= 0.1
Load Voltage (primary)
10
SF= 10
Source Voltage
11
SF= 0.1
Source Voltage (primary)
12
SF = 1
KVA
13
SF = 1
KVAR
14
SF = 1
KW
15
SF= 100
Power Factor
16
SF = 10
P2 Ratio
17
variable
Ld Current Dmd (Fwd Present)
18
SF = 1
kVA Dmd (Fwd Present)
19
SF = 1
kVAR Dmd (Fwd Present)
20
SF = 1
kW Dmd (Fwd Present)
21
SF= 10
Load Volts Dmd (Fwd Present)
22
SF= 10
CompVolts Dmd (Fwd Present)
23
variable
Load I Dmd (Rev Present) (Amps)
24
SF = 1
kVA Load Dmd (Rev Present)
25
SF = 1
kVAR Load Dmd (Rev Present)
26
SF = 1
kW Load Dmd (Rev Present)
27
SF= 10
Load Volts Dmd (Rev Present) (Volts)
28
SF= 10
Comp Volts Dmd (Rev Present)
29
SF= 10
Max % Boost or Min % Buck (%)
30
SF= 10
Max % Buck or Min % Boost (%)
31
SF= 10
Motor Voltage
32
SF= 10
Vsrc Fwd Dmd
33
SF= 10
Vsrc Rev Dmd
34
SF= 10
Vload dc offset
35
SF= 10
Vload fundamental, RMS
36
SF= 10
Vload 2nd harmonic, RMS
37
SF= 10
Vload 3rd harmonic, RMS
38
SF= 10
Vload 4th harmonic, RMS
39
SF= 10
Vload 5th harmonic, RMS
40
SF= 10
Vload 6th harmonic, RMS
41
SF= 10
Vload 7th harmonic, RMS
42
SF= 10
Vload 8th harmonic, RMS
43
SF= 10
Vload 9th harmonic, RMS
44
SF= 10
Vload 10th harmonic, RMS