LMV Series
Technical Instructions
LV3-1000
Gas
Oil
Gas
Oil
U/S/O
Default
Range
Description
Parameter #
Fuel 0
Fuel 1
LEGEND -
Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
Parameter Name
Max Time Start
Release
O
35 sec
0.2-600 sec
On gas trains, this sets the maximum amount of time before input X5-01.2 must be energized after
receiving a call for heat. Typically a low gas pressure switch and / or other start releases are wired to input
X5-01.2 on gas trains. On oil trains, this sets the maximum amount of time before input X5-02.2 must be
energized after receiving a call for heat. Typically a high oil pressure switch and / or other start releases are
wired to input X5-02.2 on oil trains.
Repetition SL
S
1
1-16
Sets how many times the LMV3 will attempt to restart without manual reset when the safety loop is
opened. This parameter should always be set to 1 (no repetitions). A setting of 16 indicates unlimited
repetitions.
Max Time Home Run
O
30 sec
5-600 sec
Sets the maximum time to satisfy all conditions required in phase 10 (home run). Two of the conditions
that must be met are the air pressure switch input X3-02.1 is de-energized and the actuators have reached
their home position. On oil trains, this also sets the maximum time to satisfy the low oil pressure switch in
phase 38. The low oil switch is wired to input X9-04.2. This parameter only has effect on the low oil
pressure switch if parameter 276 (fuel 0) or 376 (fuel 1) are set to 1. If parameter 276 or 376 are set to 2,
the low oil pressure switch must be made by the beginning of safety time 1 (phase 40).
221
261
321
361
Flame Detector
Select
1
0-1
This parameter sets the type of flame scanner that is connected to the LMV3.
0 = QRB… flame scanner (Europe)
1 = QRA… flame scanner or flame rod (North America)
222
262
322
362
Skip Prepurge
1
0-1
Activates or deactivates prepurge. It is recommended that the prepurge be activated for most burners in
North America.
0 = deactivated
1 = activated
Repetition LGPS
1
1-16
Sets how many times the LMV3 will attempt to proceed past phase 22 if the low gas pressure switch and /
or other start releases wired to input X5-01.2 are not made. After this number of tries, a lockout will occur.
A setting of 16 indicates unlimited repetitions.
225
265
325
365
Prepurge Time
30 sec
5-3600 sec
Sets the prepurge time (phase 30). Prepurge time will begin once the actuators / VSD have reached their
prepurge positions and the air pressure switch input X3-02.1 is energized.
226
-
326
-
2 sec
0.4-3600 sec
-
266
-
366
2 sec
0.6-3600 sec
The period of time that the ignition transformer (output X4-02.3) is energized before the pilot valve (output
X7-02.3) for piloted fuel trains. The function is similar for direct ignition fuel trains, except that the timing is
before the main valves (outputs X8-02.1 and X7-01.3) instead of the pilot valves. In summary, sets the
length of phase 38. On oil trains, this setting has no effect if parameter 281 (fuel 0) or 381 (fuel 1) is set to
1.
223
323
214
215
217
Pre-Ignition Time
S
SCC Inc.
Page 7
Section 3
Содержание LMV3 series
Страница 1: ...Combustion Controls LMV3 Linkageless Burner Management System www scccombustion com ...
Страница 2: ...Intentionally Left Blank ...
Страница 18: ...Technical Instructions LMV Series Document No LV3 1000 Section 1 Page 14 SCC Inc Intentionally Left Blank ...
Страница 20: ...Technical Instructions LMV Series Document No LV3 1000 Section 1 Page 16 SCC Inc Intentionally Left Blank ...
Страница 26: ...Technical Instructions LMV Series Document No LV3 1000 Section 1 Page 22 SCC Inc Intentionally Left Blank ...
Страница 40: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 12 SCC Inc 2 4 Wiring Diagrams ...
Страница 41: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 13 Section 2 ...
Страница 42: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 14 SCC Inc ...
Страница 43: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 15 Section 2 ...
Страница 44: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 16 SCC Inc ...
Страница 45: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 17 Section 2 ...
Страница 46: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 18 SCC Inc ...
Страница 76: ...Technical Instructions LMV Series Document No LV3 1000 Section 3 Page 28 SCC Inc Intentionally Left Blank ...
Страница 102: ...Technical Instructions LMV Series Document No LV3 1000 Section 4 Page 24 SCC Inc Intentionally Left Blank ...
Страница 158: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 24 Section 6 Intentionally Left Blank ...
Страница 178: ...Technical Instructions LMV Series Document No LV3 1000 Section 7 Page 18 SCC Inc Intentionally Left Blank ...
Страница 190: ...Technical Instructions LMV Series Document No LV3 1000 Section 8 Page 10 SCC Inc Intentionally Left Blank ...
Страница 223: ...Intentionally Left Blank ...