9/25
Building Technologies
CC1N7101en
HVAC Products
27.11.2008
Technical data
Mains voltage
AC 120 V +10% / -15%
AC 230 V +10% / -15%
Mains frequency
50...60Hz ±6%
Power consumption
12VA
External primary fuse (Si)
Max. 10A (slow)
Mounting position
Optional
Input current at terminal 12
Max. 5A
Weight Approx.
160g
Safety class
I
Degree of protection
IP40 (to be ensured through mounting)
Perm. cable length terminal 1
Max. 1m at a line capacitance of 100pF/m
(max. 3m at 15pF/m)
Perm. cable length from QRA… to
AGQ3…A27 (lay separate cable)
Max. 20m at 100pF/m
Remote reset laid separately
Max. 20m at 100pF/m
Perm. cable length terminals 8 and 10
Max. 20m at 100pF/m
Perm. cable lengths other terminals
Max. 3m at 100pF/m
Perm. terminal load
At cos
ϕ
≥
0.6
At cos
ϕ
= 1
- Terminal 3
Max. 2.7A
(15A for max. 0.5s
→
only LME2…)
Max. 3A
- Terminals 4, 5, 7 and 9 (11) Max. 1.7A
Max. 2A
- Terminal 10
Max. 1A
Max. 1A
Storage
DIN EN 60721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-20...+60°C
Humidity <95%
r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions
Class 2K2
Mechanical conditions
Class 2M2
Temperature range
-20...+60°C
Humidity <95%
r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions
Class 3K3
Mechanical conditions
Class 3M3
Temperature range
-20...+60°C
Humidity <95%
r.h.
Condensation, formation of ice and ingress of water are not permitted!
* The designed lifetime is not the warranty time specified in the Terms of Delivery
General unit data
Environmental
conditions