background image

GAMMA instabus

Technical Product Information

February 2013

IP Controller N350E

5WG1 350-1EB01

Siemens AG

N350E, 4 Seiten

Technical manual

Infrastructure & Cities Sector, Building Technologies
Control Products and Systems

© Siemens AG 2013

Update: http://www.siemens.com/gamma

P.O. Box 10 09 53, D-93009 Regensburg

Subject to change without further notice

2.12.1.12/3

Location and Function of the Display and
Operator Elements

Figure 1: Location of the display and operator elements

A1    AC/DC 24 V bus connector terminal (yellow-white)
A2    KNX bus connector terminal (black-red)
A3    Ethernet RJ45 socket
A4    KNX programming LED
A5    KNX learning button
A6    Display 2x12 characters
A7    MOVE push button
A8    Set/Prg push button
A9    ESC push button
A10  Ethernet Link LED
A11  Ethernet Activity LED
A12  Battery case

Setting time and date
In the display mode the LC-display shows time, day of
week, and date. Switch to the setup mode by depressing
the Set/Prg-push button (A8). Hour – Minute – Day –
Month – Year can be set in this order. Move from one to
the next with the Set/Prg-push button (A8). The selected
time/date value can be set by depressing the Move push
button (A7). Scroll through until the correct value is
displayed and then press the Set/Prg-push button (A8) to
move to the next time/date value.
After you entered the value for the year press the
Set/Prg-push button (A8). The device automatically
leaves the setup mode after approximately five seconds.
The setup mode can be left by pressing the ESC push
button (A9).

Mounting and Wiring

General description
The N-system DIN-rail device can be installed in distribu-
tion boards, surface or flush mounted, or on any DIN rail
complying with EN 60715-TH35-7,5.
The connection to the bus line is established via the bus
connector terminal (red-black) on the top side.
The RJ45 socket on the device front side provides the
connection to the Ethernet-IP data network.

Mounting DIN-rail devices (Figure 2)

-

Slide the device (Figure 2, B1) onto the DIN-rail (Figure
2, B2) and

-

swivel back the device until the slide clicks into place
audibly.

-

Connect the auxiliary power AC/DC 24V with the yel-
low-white bus connector terminal (A1).

-

Connect the bus line with the black-red bus connector
terminal (A2).

-

Plug an Ethernet patch cable with an RJ45 plug into
the RJ45 socket (A3) to connect the device with the
LAN / Intranet.
A connection is established to the network when the
yellow LED marked LK (A10) is continuously lit. When
the LED LA (A11) flashes data is sent to or from the de-
vice.

Dismounting DIN-rail devices

-

Unplug the Ethernet patch cable from the RJ45 socket
(Figure 1, A3).

-

Remove the yellow-white bus connector terminal (Fig-
ure 1, A1) from its socket.

-

Remove the black-red bus connector terminal (Fig-
ure 1, A2) from its socket.

-

press down the slide (Figure 2, C3) with a screw-driver
and

-

swivel the device (Figure 2, C1) from the DIN-rail (Fig-
ure 2, C2).

B1

C1

C2

C3

B2

Figure 2: Mounting and dismounting a DIN-rail device

Содержание IP Controller N350E

Страница 1: ... zone selection for automatic time synchroniza tion Automatic Daylight Savings Time change over se lectable DHCP for automatic IP address assignment Communication via IP network with a visualization software ETS3 acting as a configuration interface Via ETS up to 80 objects can be defined for the device with free data type assignment from this list of data types 1 bit EIS1 1 Byte unsigned EIS 14 1 ...

Страница 2: ...V Recommended power supplies DC 24V before choke from KNX power supplies N125 x2 Control elements 1 learning button for switching between normal operating mode and addressing mode 3 push buttons Move Prg Set ESC on the front side to locally set date and time and to display IP address MAC address and firmware version of the device Display elements 1 yellow LED Ethernet Link Signal available LK 1 ye...

Страница 3: ...ce automatically leaves the setup mode after approximately five seconds The setup mode can be left by pressing the ESC push button A9 Mounting and Wiring General description The N system DIN rail device can be installed in distribu tion boards surface or flush mounted or on any DIN rail complying with EN 60715 TH35 7 5 The connection to the bus line is established via the bus connector terminal re...

Страница 4: ...e approx 5 mm of insulation from the conduc tor D2 4 and plug it into the bus connection block D2 red black Disconnecting bus cables Figure 3 Unplug the bus connection block E1 and remove the bus cable conductor E1 4 while simultaneously wig gling it D2 D D2 D2 4 5 mm D2 D2 4 D2 1 D2 2 D2 D2 3 Figure 3 Connecting and disconnecting bus wires Slipping off on auxiliary power connection block Follow t...