GAMMA instabus
Technical Product Information
February 2013
IP Controller N350E
5WG1 350-1EB01
Siemens AG
N350E, 4 Seiten
Technical manual
Infrastructure & Cities Sector, Building Technologies
Control Products and Systems
© Siemens AG 2013
Update: http://www.siemens.com/gamma
P.O. Box 10 09 53, D-93009 Regensburg
Subject to change without further notice
2.12.1.12/3
Location and Function of the Display and
Operator Elements
Figure 1: Location of the display and operator elements
A1 AC/DC 24 V bus connector terminal (yellow-white)
A2 KNX bus connector terminal (black-red)
A3 Ethernet RJ45 socket
A4 KNX programming LED
A5 KNX learning button
A6 Display 2x12 characters
A7 MOVE push button
A8 Set/Prg push button
A9 ESC push button
A10 Ethernet Link LED
A11 Ethernet Activity LED
A12 Battery case
Setting time and date
In the display mode the LC-display shows time, day of
week, and date. Switch to the setup mode by depressing
the Set/Prg-push button (A8). Hour – Minute – Day –
Month – Year can be set in this order. Move from one to
the next with the Set/Prg-push button (A8). The selected
time/date value can be set by depressing the Move push
button (A7). Scroll through until the correct value is
displayed and then press the Set/Prg-push button (A8) to
move to the next time/date value.
After you entered the value for the year press the
Set/Prg-push button (A8). The device automatically
leaves the setup mode after approximately five seconds.
The setup mode can be left by pressing the ESC push
button (A9).
Mounting and Wiring
General description
The N-system DIN-rail device can be installed in distribu-
tion boards, surface or flush mounted, or on any DIN rail
complying with EN 60715-TH35-7,5.
The connection to the bus line is established via the bus
connector terminal (red-black) on the top side.
The RJ45 socket on the device front side provides the
connection to the Ethernet-IP data network.
Mounting DIN-rail devices (Figure 2)
-
Slide the device (Figure 2, B1) onto the DIN-rail (Figure
2, B2) and
-
swivel back the device until the slide clicks into place
audibly.
-
Connect the auxiliary power AC/DC 24V with the yel-
low-white bus connector terminal (A1).
-
Connect the bus line with the black-red bus connector
terminal (A2).
-
Plug an Ethernet patch cable with an RJ45 plug into
the RJ45 socket (A3) to connect the device with the
LAN / Intranet.
A connection is established to the network when the
yellow LED marked LK (A10) is continuously lit. When
the LED LA (A11) flashes data is sent to or from the de-
vice.
Dismounting DIN-rail devices
-
Unplug the Ethernet patch cable from the RJ45 socket
(Figure 1, A3).
-
Remove the yellow-white bus connector terminal (Fig-
ure 1, A1) from its socket.
-
Remove the black-red bus connector terminal (Fig-
ure 1, A2) from its socket.
-
press down the slide (Figure 2, C3) with a screw-driver
and
-
swivel the device (Figure 2, C1) from the DIN-rail (Fig-
ure 2, C2).
B1
C1
C2
C3
B2
Figure 2: Mounting and dismounting a DIN-rail device