background image

GAMMA instabus

Technical Product Information

February 2013

IP Controller N350E

5WG1 350-1EB01

Technical manual

N350E, 4 Seiten

Siemens AG

Infrastructure & Cities Sector, Building Technologies

Update: http://www.siemens.com/gamma

© Siemens AG 2013

Control Products and Systems

Subject to change without further notice

P.O. Box 10 09 53, D-93009 Regensburg

2.12.1.12/2

Installation Instructions

·

The device may be used for permanent interior instal-
lations in dry locations within distribution boards or
small casings with DIN rail EN 60715-TH35-7,5.

V

WARNING

·

The device must be mounted and commissioned by an
authorised electrician.

·

The device may be mounted to switch and socket
combination box mounts if VDE-certified devices are
used exclusively.

·

The prevailing safety rules must be heeded.

·

For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.

Technical Specifications

Network communication

·

Ethernet:
10BaseT (10 Mbit/s)

·

Supported Internet Protocols:
ARP, ICMP, IGMP, UDP/IP, DHCP

·

KNXnet/IP according to KNX System Specification:
Core, Device Management

Rated voltage

·

Bus: DC 24V (DC 21...30V)

·

Auxiliary power supply:
AC/DC 24V (AC/DC 12...30V)

Power supply

·

Bus voltage: via KNX bus line

·

Operating voltage:
from external SELV power supply AC/DC 24V nominal,
permissible input voltage range:
AC/DC 12 ... 30 V

·

Recommended power supplies:
– DC 24V (before choke) from KNX power supplies
N125/x2

Control elements

·

1 learning button:
for switching between normal operating mode and
addressing mode

·

3 push buttons (Move, Prg/Set, ESC):
on the front side to locally set date and time and to

display IP address, MAC address and firmware version
of the device

Display elements

·

1 yellow LED: Ethernet Link Signal available (LK)

·

1 yellow LED: Data transmission on Ethernet (LA)

·

1 red LED: for monitoring bus voltage and displaying
mode, selected with the learning button

·

LC-Display, 2 rows with 12 characters each to display
date and time

Connections

·

bus line:  screwless bus connection block (red-black)
0,6...0,8 mm Ø single core

·

Ethernet / IP network: RJ45 socket

·

auxiliary power:
screwless extra low voltage terminal (yellow-white)

Æ

 0,6 ... 0,8 mm Ø single core

Physical specifications

·

housing: plastic

·

DIN-rail mounted device,
width: 2 SUs (1SU = 18mm), height: 55 mm

·

installation: rapid mounting on EN 60715-TH35-7,5 rail

·

weight: approx. 150g

Electrical safety

·

degree of pollution (according to IEC 60664-1): 2

·

protection (according to EN 60529): IP 20

·

overvoltage class (according to IEC 60664-1): III

·

bus: safety extra low voltage SELV DC 24 V

·

the device complies with EN 50 090-2-2

Electromagnetic compatibility
complies with EN 50090-2-2

Environmental specifications

·

climatic conditions: EN 50090-2-2

·

ambient temperature operating: 0 ... + 45

°

C

·

storage temperature: - 25 ... + 70

°

 C

·

relative humidity (non-condensing): 5 % to 93 %

Markings
EIB, KNX, CE

CE mark
complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations

Содержание IP Controller N350E

Страница 1: ... zone selection for automatic time synchroniza tion Automatic Daylight Savings Time change over se lectable DHCP for automatic IP address assignment Communication via IP network with a visualization software ETS3 acting as a configuration interface Via ETS up to 80 objects can be defined for the device with free data type assignment from this list of data types 1 bit EIS1 1 Byte unsigned EIS 14 1 ...

Страница 2: ...V Recommended power supplies DC 24V before choke from KNX power supplies N125 x2 Control elements 1 learning button for switching between normal operating mode and addressing mode 3 push buttons Move Prg Set ESC on the front side to locally set date and time and to display IP address MAC address and firmware version of the device Display elements 1 yellow LED Ethernet Link Signal available LK 1 ye...

Страница 3: ...ce automatically leaves the setup mode after approximately five seconds The setup mode can be left by pressing the ESC push button A9 Mounting and Wiring General description The N system DIN rail device can be installed in distribu tion boards surface or flush mounted or on any DIN rail complying with EN 60715 TH35 7 5 The connection to the bus line is established via the bus connector terminal re...

Страница 4: ...e approx 5 mm of insulation from the conduc tor D2 4 and plug it into the bus connection block D2 red black Disconnecting bus cables Figure 3 Unplug the bus connection block E1 and remove the bus cable conductor E1 4 while simultaneously wig gling it D2 D D2 D2 4 5 mm D2 D2 4 D2 1 D2 2 D2 D2 3 Figure 3 Connecting and disconnecting bus wires Slipping off on auxiliary power connection block Follow t...