Electrical Installation Technology 

 

Subject to change without further notice 

P.O. Box 10 09 53, D-93009 Regensburg 

2.5.3.1/4 

Dismantling the DIN rail mounted device (Diagram 2) 
-

 

Remove all the connected cables, 

-

 

press the slide switch (C3) downwards with a 
screwdriver and  

-

 

remove the DIN rail mounted device (C1) from the DIN 
rail (C2) with a swivel action. 

 

B1

C1

C2

C3

B2

 

 

Figure 2: 

Installing / dismantling the DIN rail mounted 

device 

 

Removing the bus terminal (Figure 3) 
-

 

The bus terminal is located on the top of the N 525E 
(D1) 

-

 

The bus terminal (D2) consists of two sections (D2.1, 
D2.2), each with four terminal contacts. Care should 
be taken not to damage the two test sockets (D2.3), 
either by accidentally connecting them to the bus 
conductor or with the screwdriver (when trying to 
remove the bus terminal).

 

-

 

Carefully insert the screwdriver in the wire entry slot 
underneath the bus terminal (D2) and pull the bus 
terminal forwards out of the N 525E (D1).

 

 

Note: 

Care should be taken as there is a risk of shorting 

the device!

 

 

Connecting the bus terminal (Figure 3) 

-

 

Place the bus terminal in the guide slot and press the 
bus terminal (D2) backwards until it reaches the stop.

 

 

Connecting the bus cable (Figure 3) 
-

 

The bus terminal (D2) is suitable for single-core 
conductors with 0.6... 0.8 mm Ø. 

-

 

Strip approx. 5 mm of insulation from the conductor 
(D2.4) and plug in the terminal (D2) (red=+, black=-).

 

 

Disconnecting the bus cable (Figure 3)  
-

 

Remove the bus terminal (D2) and the conductor 
(D2.4) out of the bus cable by rotating it backwards 
and forwards. 

-

 

D1

D2

D2

D2.4

D2

D2.4

5 mm

D2.1 D2.2

2

D2.3

 

D

 

 

Figure 3: 

Connecting and disconnecting the cable

 

 

Connecting mains voltage and DALI bus cables 
-

 

The connections are designed with plug-in technology. 

-

 

Strip approx. 10-11 mm of insulation from the conduc-
tors and slide in the respective terminal. 

Cross-sections:  

 

The following conductor cross-sections are permitted: 

-

 

0.5 ... 3.3 mm2 (AWG 12) single-core  

-

 

0.5 ... 3.3 mm2 (AWG 12) stranded multi-core  

-

 

0.5 ... 3.3 mm² (AWG 12) finely stranded, untreated  

-

 

0.5 ... 1.5 mm2 finely stranded, with connector 
sleeve 

 

The mains connection must be fused with a circuit-
breaker of characteristic B or C with a max. nominal 
current of 6 A! 

 

Mounting the insulating cap

 

-

 

If the device should be mounted on a DIN rail without 
a data rail, the contact system must be covered with 
the supplied insulating cap. 

Removing the locating clamp

 

(Figure 4) 

-

 

The locating clamp (E3) encloses the contact system 
(E2) on the rear of the DIN rail mounted device (E1). 

-

 

Insert the screwdriver between the DIN rail mounted 
device (E1) and the locating clamp (E3) and remove 
the clamp. 

 

Clipping on the insulating cap: (Figure 4) 

-

 

Place the insulating cap (E4) on the contact system and 
press so that it snaps in place.

 

 
 
 
 
 
 
 
 
 

Содержание Instabus/DALI Gateway N 141

Страница 1: ...pplies the gateway electronics and generates the DALI bus voltage Additionally it enables the operation of the gateway and a direct switching of all lamps controlled over its DALI output even if the N 141 has not yet been commissioned with the ETS or if the communication via the EIB has been interrupted For this purpose the N 141 has a pushbutton located bottom left on its front plate for switchin...

Страница 2: ...EIB bus current 5 mA only half a standard bus load Electronics and DALI output integrated power supply for AC DC 110 240 V 50 400 Hz power consumption max 7 W Inputs outputs Mains connection 3 pole PE N L DALI output according to IEC 60929 max 64 DALI devices with 8 kOhm input impedance DALI bus voltage approx DC 19 V floating short circuit proof Operating elements 1 learning push button for toggl...

Страница 3: ... A5 A7 A10 A9 A8 A6 Figure 1 Location of the display and operating elements A1 Button for toggling between normal addressing mode for transferring the physical address A2 LED red for displaying normal mode LED off or addressing mode LED on it is automatically extinguished once the physical address has been transferred A3 Plug for bus connecting terminal A4 Pushbuttons for direct operation all lamp...

Страница 4: ...it reaches the stop Connecting the bus cable Figure 3 The bus terminal D2 is suitable for single core conductors with 0 6 0 8 mm Ø Strip approx 5 mm of insulation from the conductor D2 4 and plug in the terminal D2 red black Disconnecting the bus cable Figure 3 Remove the bus terminal D2 and the conductor D2 4 out of the bus cable by rotating it backwards and forwards D1 D2 D2 D2 4 D2 D2 4 5 mm D2...

Страница 5: ...10 09 53 D 93009 Regensburg Subject to change without further notice 2 5 3 1 5 Figure 4 Covering the contact system Dimension drawing Dimensions in mm b 90 44 55 45 b 4 module units 1 module unit 18 mm General notes Any faulty devices should be returned to the local Siemens office If you have further questions about the product please contact our Technical Support 49 0 180 50 50 222 49 0 180 50 50...

Отзывы: