Interface modules IM 153-4 PN and IM 153-2 HF
12
A5E02714951-AH, 07/2019
Changes to the IM 153-4AA0x as compared to the ET 200M operating instructions
The following changes have been made:
Property
6ES7153-4AA01-0XB0
6ES7153-4BA00-0XB0
Shared device
x
x
Media redundancy
x
x
Isochronous real-time communication
IRT option "high performance"
x
x
Fail-safe modules
—
x
Connection to H-CPUs with system redundancy
—
x
HART modules
—
x
Configuration with STEP 7 or GSD
You can configure the ET 200M:
●
6ES7153-4AA01-0XB0, V4.0 under
–
STEP 7 (TIA Portal) V11 SP2, HSP0028 or
–
STEP 7 Classic V5.5.2.0, HSP0223
●
6ES7153-4BA00-0XB0, V4.0 under
–
STEP 7 (TIA Portal) V11 SP2, HSP0028 or
–
STEP 7 Classic V5.5.2.1, HSP0220
●
Or with GSD file
You can find the GSD file at Internet (
http://support.automation.siemens.com/WW/view/en/25057900
The F modules of the 6ES7153-4BA00-0XB0 can only be configured with STEP 7.
You can configure the HART modules
●
6ES7331-7TF01-0AB0
●
6ES7331-7TB00-0AB0
●
6ES7332-8TF01-0AB0
●
6ES7332-5TB00-0AB0
with STEP 7 V5.5 SP3 and SIMATIC PDM V8.0 SP2 (HART on PROFINET).
IM 153-2BAx2
The following changes have been made to the technical specifications of the 6ES7153-2BAx2-0XB0 as of product version
02:
Voltage, Currents, Potentials
Current consumption from 24 V
max. 600 mA (for 6ES7153-2BAx2, product version 01)
max. 620 mA (for 6ES7153-2BAx2, product version 02)
IM 153-2BA10/IM 153-2BA70
There are two new interface modules:
●
IM 153-2BA10-0XB0 (replacement part and compatible functional successor for IM 153-2BA02-0XB0)
●
IM 153-2BA70-0XB0 (replacement part and compatible functional successor for IM 153-2BA82-0XB0)