Siemens IGWiPS200-1 Скачать руководство пользователя страница 7

 

IGWiPS200-1 

Each transceiver and each I/O Expansion module has bus connectors on both sides of its cover: a male connector on 
one side, a female connector on the other. A transceiver and several I/O Expansion modules can be physically 
interconnected by way of their bus connectors and then snapped onto a section of DIN rail as a single unit. These 
bus connectors carry signal, power, and ground connections between the interconnected devices. 
 
An easy to use wireless network Configurator is available at the Siemens Internet site to help you select remote 
transceivers and I/O expansion modules. A master transceiver and one remote transceiver are the configuration 
starting point. When adding an I/O module to a remote transducer, the complementary module is automatically 
added to the master transceiver. For example, adding an 8-Channel Digital Input Module to a remote transceiver will 
cause an 8-Channel Digital Output Module to be automatically added to the master transceiver. The online 
Configurator totals the number of I/O Expansion modules and displays a warning if the maximum quantity is 
exceeded. 
 

Table 1  WiPS Series 200 Multipoint-To-Point Transceivers and I/O Expansion Modules 

 

WiPS Model 
Number 

Transceiver and I/O Expansion Modules 

(see Notes below) 

Order 

Number 

WiPS-20 Unconfigured 

Transceiver 

TGX:16347-320 

WiPS-22 

8-Channel Digital Input Module 

TGX:16347-322 

WiPS-23 

8-Channel Digital Output Module 

TGX:16347-323 

WiPS-24 

4-Channel Analog Input Module 

TGX:16347-324 

WiPS-25 

4-Channel Analog Output Module 

TGX:16347-325 

Combination Input/Output Module with:  

WiPS-26 

 

1 analog input channel 
1 analog output channel 
2 digital input channels 
2 digital output channels 

TGX:16347-326 

WiPS-27 

2-Channel Pulse Input Module 

TGX:16347-327 

WiPS-28 

2-Channel Pulse Output Module 

TGX:16347-328 

Notes: 
Order antennas, antenna cable, power supplies, and other accessories separately. 
Siemens Logo power supply is part number 6EP13311SH02. 
All 200 Series transceivers and I/O Expansion module have bus connectors for distribution of power and data. 
 
A WiPS Series 200 transceiver is a frequency hopping spread spectrum radio designed for professional installation 
and integration with other products. When installed with an approved antenna and cable, the system integrator needs 
to make sure that the unit’s FCC label is clearly visible on the outside of the integrated product. WiPS is approved 
within the 902 to 928 MHz ISM band under 47CFR15.247 of the FCC Rules and Regulations.  
 
Frequency hopping spread spectrum technology was originally developed by the U.S. military to prevent 
interference or interception of radio transmissions on the battlefield. Frequency hopping devices concentrate their 
full power into a very narrow signal and randomly hop from one frequency to another within a designated frequency 
band. If they encounter interference on a particular frequency, the devices error-check the affected data, hop to 
another point on the spectrum, and resume communications on subsequent hops. Since there are always spaces 
without interference somewhere in the allotted radio spectrum, a frequency hopping device will use those spaces to 
complete a transmission. 

IMPORTANT 

 

Save this Installation Guide and have it available when installing the above products. 

May 2007 

Содержание IGWiPS200-1

Страница 1: ...ALLATION GUIDE IGWiPS200 1 Rev 3 May 2007 WiPS 200 Series Wireless Process Solution Frequency Hopping Spread Spectrum Radio Two Way Multipoint to Point for Monitoring and Control With Expandable I O Options ...

Страница 2: ......

Страница 3: ... LED INDICATIONS 30 PULSE INPUT MODULE DIAGNOSTIC LED S 30 PULSE OUTPUT MODULE DIAGNOSTIC LED S 31 SPECIFICATIONS 31 WARRANTY 34 LIST OF FIGURES FIGURE AND TITLE PAGE Figure 1 Sample Installation 7 Figure 2 Current Amperage Budget Example 10 Figure 3 Physical Dimensions 14 Figure 4 Module Features 15 Figure 5 Removing a Connector Block 17 Figure 6 Transceiver Wiring 4 20 mA Current Loop with 2 Wir...

Страница 4: ...e presence of an electrical shock hazard The associated text states the nature of the hazard Explosion hazard Symbol indicates that the danger of an explosion hazard exists The associated text states the nature of the hazard Electrostatic discharge The presence of this symbol indicates that electrostatic discharge can damage the electronic assembly Pinch hazard Symbol indicates that a pinch hazard...

Страница 5: ...rinsically safe device loses its license as soon as it is operated in a circuit that does not meet the requirements of the examination certificate valid in your country The device may be operated with high pressure and corrosive media Therefore serious injury and or considerable material damage cannot be ruled out in the event of handling of the device The perfect and safe operation of the equipme...

Страница 6: ... 1 4 Wave Antenna Typical I O Expansion Module Siemens Logo Power Supplies Two types of transceivers are provided Master and Remote i e Slave2 The master transceiver is installed at a central data collection and processing location such as a control room Remote transceivers are installed near field devices such as transmitters counters motors fans conveyer belts stirrers and annunciators Each wire...

Страница 7: ... Combination Input Output Module with WiPS 26 1 analog input channel 1 analog output channel 2 digital input channels 2 digital output channels TGX 16347 326 WiPS 27 2 Channel Pulse Input Module TGX 16347 327 WiPS 28 2 Channel Pulse Output Module TGX 16347 328 Notes Order antennas antenna cable power supplies and other accessories separately Siemens Logo power supply is part number 6EP13311SH02 Al...

Страница 8: ...site see the table below has current revisions of technical publications in Portable Document Format for downloading To send an instrument to Siemens for repair contact Siemens and request a Return Material Authorization RMA IMPORTANT An instrument must be thoroughly cleaned decontaminated to remove any process materials hazardous materials or blood born pathogens prior to return for repair Read a...

Страница 9: ...is section The highly directional Yagi antenna shown below is used when data transmission over longer distances is necessary An omnidirectional whip antenna is used for shorter distances and when a circular radiation pattern is desired often due to the wide physical distribution of remote transceivers Regardless of antenna type a surge arrestor is highly recommended particularly in out of doors in...

Страница 10: ...bel and a wiring label The nameplate label carries the module s part number agency approvals and other data The wiring label identifies the connection terminals Sample labels are shown here To assist module identification color coded faceplate labels are provided Transceiver White 4 Channel Analog Input Green 4 Channel Analog Output Yellow 8 Channel Digital Input Blue 8 Channel Digital Output Pink...

Страница 11: ...pment described in this publication in installed without safety barriers the following precautions should be observed Switch off electrical power at its source in non hazardous location before connecting or disconnecting power signal or other wiring Précautions Français Emplacements dangereux de classe I division 2 Les pièces de rechange doivent être autorisées par l usine Les substitutions peuven...

Страница 12: ...interconnects a transceiver and its connected I O modules see Figure 2 The current on this bus may not exceed 5A This section shows how to calculate the current flowing on the common current bus Note that the calculations in this section are also useful when determining power supply requirements at each transceiver location Figure 2 shows a two node remote site and control room wireless network Th...

Страница 13: ... 1 DIN rail s mounting hardware and enclosure s appropriate to the environment and hazardous area certification 2 Signal and power wiring and appropriate tools for wire preparation e g wire cutters and strippers 3 Conduit tubing adapters and outlet boxes and appropriate tools for cutting and routing conduit 4 Circuit protection devices e g fuses circuit breakers on off switches Electrostatic Disch...

Страница 14: ...he DC bias exceeds 3 6V such as in a ground loop condition All other applications including an AC sine wave input should be set to DC Coupling Switch 2 Input Impedance Low or High Default setting is High The Low impedance setting has an input impedance of 1K Ohm and the High setting has an impedance of 90K Ohm Use the High impedance setting for magnetic transducers to prevent the current draw from...

Страница 15: ... for photographs alternatively label each wire to facilitate reconnection and then disconnect the wires Physically separate interconnected modules to disconnect the common current bus connectors Use a small straight slot screwdriver to lever the spring loaded module mounting lip away from the DIN rail allowing that module to slide on the rail Remove the module from the DIN rail 3 Remove the facepl...

Страница 16: ... The DIN rail must be grounded When mounting the DIN rail in a non conductive enclosure install a ground wire between the rail and the single point ground DIN Rail Mount Transceiver or I O Expansion Module Figure 3 Physical Dimensions MOUNTING A TRANSCEIVER OR I O MODULE I O Expansion Modules may be mounted on a section of DIN rail in any sequence Mount the Transceiver at either end of the row of ...

Страница 17: ...ient the module and hook the module s fixed mounting lip on the DIN rail 3 Press the module against the DIN rail until the spring loaded mounting lip snaps onto the rail 4 Slide the module to one side until the bus connector mates with the adjacent module A module will easily slide on the DIN rail if the spring loaded lip is levered away from the rail 5 As required place a bus connector cover supp...

Страница 18: ...act with the grounded bracket 4 Thread the antenna onto the stud and tighten 5 Once the transceiver is installed plug the MCX male connector on the end of the antenna cable into the MCX female connector on the transceiver faceplate WIRING This section provides wiring guidelines for the transceiver and I O Expansion modules A wireless network contains a master transceiver and up to eight matched re...

Страница 19: ...emes Use supply wires suitable for 5 C 10 F above ambient temperature exposure to sunlight vibration types of contaminates Wire Routing and Conduit DC wiring should be separated from AC wiring and away from AC powered pushbuttons alarms annunciators motors solenoids and similar devices Conduit and raceways are commonly used for routing wiring Wiring not installed in conduit or raceway should be cl...

Страница 20: ...e wiring for an RF Link annunciator which can be an input to a PLC or controller or a separate light or siren A digital output wiring example is provided in Figure 9 The transceiver is DC powered typically by a DIN rail mount power supply as shown below The power supply for the transceiver also powers the connected I O modules Power is supplied through the transceiver and across the common current...

Страница 21: ...IGWiPS200 1 Figure 7 Transceiver Wiring 4 20 mA Current Loop with 3 Wire Device May 2007 19 ...

Страница 22: ...IGWiPS200 1 Figure 8 Transceiver Wiring 4 20 mA Current Loop with 4 Wire Device May 2007 20 ...

Страница 23: ...IGWiPS200 1 Figure 9 Transceiver Wiring Analog and Digital Outputs Figure 10 Transceiver Wiring Analog Output Wiring for a Loop Powered Device May 2007 21 ...

Страница 24: ...connect an analog or digital signal as described below when an RF link is lost Refer to the Specifications section for relay contact rating For additional information about RF Link response refer to Transceiver and I O Expansion Module Status LEDs on page 30 Transceiver Analog and Digital Output Last State Selection The default state upon loss of RF link for the analog and digital outputs is MAINT...

Страница 25: ...IGWiPS200 1 Green Faceplate Figure 12 4 Channel Analog Input Module Wiring Yellow Faceplate Figure 13 4 Channel Analog Output Module Wiring May 2007 23 ...

Страница 26: ...IGWiPS200 1 Blue Faceplate Figure 14 8 Channel Digital Input Module Wiring Pink Faceplate Figure 15 8 Channel Digital Output Module Wiring May 2007 24 ...

Страница 27: ...IGWiPS200 1 Multiple Colors Faceplate Figure 16 Combination Input and Output Module Wiring One Analog Input One Analog Output Two Digital Inputs and Two Digital Outputs May 2007 25 ...

Страница 28: ...IGWiPS200 1 Orange Faceplate Figure 17 2 Channel Pulse Input Module Wiring Orange Faceplate Figure 18 2 Channel Pulse Output Module Wiring May 2007 26 ...

Страница 29: ...complementary Analog Input Module at the control room green faceplate are set to address 1 The small triangle symbol points to the selected module address When assigning I O module addresses Assign a module address to each complementary pair of I O modules on a wireless network An address may be used for only ONE complementary pair on each wireless network If module addresses conflict or are impro...

Страница 30: ...ansceiver and power is applied the transceiver will memorize the identification hop frequencies and hop sequence of the matched transceiver When power is removed it will retain this information even if the Hop Key is removed The newly matched transceiver and the original matched transceiver will communicate with the other matched transceiver s IMPORTANT When replacing or adding a transceiver to a ...

Страница 31: ...e the anti static wrist strap from your wrist When power is applied to the spare transceiver it will memorize Hop Key data allow a few seconds after power up for the data to transfer to transceiver memory POST INSTALLATION SIGNAL STRENGTH AND LED INDICATIONS This section describes a method for determining whether received signal strength is adequate It also provides status LED indications that wil...

Страница 32: ...emote transceivers A Remote transceiver will indicate a loss of RF Link when it cannot communicate with the master transceiver Flashes rapidly when signal strength is marginal see the RSSI graph in the Servicing section of this guide ON steady indicates an exceptionally strong RF link Most systems will flash occasionally indicating the presence of intermittent interference in the area Digital Inpu...

Страница 33: ...fied voltage levels consult factory for relay options Outputs Analog 1 4 to 20 mA 12 bit resolution short circuit protected Digital 2 250 Vac 30 Vdc 2A dry contact RF Link 1 250 Vac 30 Vdc 2A dry contact Repeatability 4 20 mA Current Loop 0 02 Accuracy 4 20 mA Current Loop 0 2 full scale Transmitter Power Output 1 Watt 30 dBm Range Standard Omnidirectional Antenna 600 to 1000 feet 183m to 305m in ...

Страница 34: ... Channels 4 Range 4 20 mA Resolution 16 bit Input Impedance 170 Ohms Channel Isolation None power supply connections are common with transceivers Reverse Polarity Protected Yes Compatibility 2 wire 3 wire 4 wire devices Over Voltage Rating 42 Vdc maximum Accuracy 0 2 of full scale Repeatability 0 02 of full scale Power Input 12 30 Vdc Current Consumption 130 mA maximum Operating Temperature Range ...

Страница 35: ...plate Label Colors Analog In section Green Analog Out section Yellow Digital In section Blue Digital Out section Pink Pulse Input Module Channels 2 Input Voltage 3 6 Vdc minimum Single Edge Mode 100 mVac P P Differential Mode Input Frequency 0 32 kHz Pulse Width 10 μSec minimum Input Impedance 1k Ohms low 90k Ohms high Selectable Coupling AC or DC Selectable Channel Isolation Optical Reverse Polar...

Страница 36: ...price which may include a full refund of the contract price for the nonconforming goods c SELLER HEREBY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED EXCEPT THAT OF TITLE SPECIFICALLY IT DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE COURSE OF DEALING AND USAGE OF TRADE d Buyer and successors of Buyer are limited to the remedies specified in this article a...

Отзывы: