5

2. Using the ICP-B6 as a Telephone Zone

When the ICP-B6 is used as a telephone zone
module, the 24 VDC provides supervision,
trouble, and call-in conditions. If the 24 VDC is
lost, the trouble condition INPUT DEVICE
RESPONSE TOO LOW displays at the MXL/
MXLV and an LED for that zone lights at the
VSM-1 module.

The supervised telephone common talk riser
starts at the TBM module in the MME-3 back-
box. The Class B shielded cable connects
continuously to each ICP-B6 with a 5.6K end of
line device. Tie the shield of these riser wires
and the shield of the zone output wires together
using terminal 5 of TB2 and isolate them from
the system circuits and the earth ground
.

Connect the supervised individual zone output
connections from each ICP-B6 to the field
telephone with shielded cable. Terminate
them at the last station with a 10K ohm end of
line resistor. As with the common talk line
described in the paragraph above, be sure
that the shield is continuous and isolated

Figure 5

ICP-B6 Used as a Telephone Zone

+

+

+

+

+

-

-

-

-

-

ANALOG LOOP

CONNECTION

FJ-303

FJ-303

BLACK

BLACK

BLACK

BLACK

WHITE

WHITE

WHITE

WHITE

SHIELD

SHIELD

SHIELD

WARDEN'S STATIONS

MODELS FT-301 SERIES

AND FT-302 SERIES

24 OHMS MAX

10K, 1/2W, +/-5%

EOL RESISTOR

P/N 140-112172

AT LAST STATION

ICP-B6 DC SUPPLY

FROM MMB, PSR-1, OR

UL LISTED POWER SUPPLY

MANUFACTURED BY ALARM-SAF
Model BN4-002-UL (SUPERVISED)

FROM PREVIOUS ICP-B6, OCC-1,

OR TBM

(20 OHMS MAXIMUM

LINE RESISTANCE)

COMMON TALK RISER

18 AWG MINUMUM

BELDON 8760 OR EQUIVALENT

OR AS REQUIRED BY

THE LOCAL AUTHORITY

HAVING JURISDICTION

RISER

NOMINAL VOLTAGE:
MAXIMUM CURRENT:

17.5 VDC

175 mA

10K, 1/2W, +/-5%

EOL RESISTOR

P/N 140-112172

AT LAST FJ-303

5.6K, 1/2W, +/-5%

EOL RESISTOR

ELECTRICAL:

INPUT DC SUPPLY:
SUPERVISORY OUTPUT:
ACTIVATED OUTPUT:

20.5 TO 30 VDC, 18mA MAX
8V, .8mA
11V, 70mA

SUPERVISED

POWER LIMITED

FROM MXL MMB OR

ALD-2I ON MOM-4

(12 MAX ICP-B6

MODULES PER LOOP)

(SUPERVISED)

NOTES:
1. THE SHIELD ON THE COMMON TALK LINE MUST BE CONTINUOUS

AND CONNECTED ONLY TO DC COMMON AT CONTROL PANEL.

2. ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES.

3. POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <5K OHMS FOR TERMINALS 3-6.

ICP-B6

ICP-B6

PROGRAM
PLUG

PROGRAM
PLUG

TB1

TB1

6

6

5

5

4

4

3

3

2

2

1

1

+

+

+

+

-

-

-

-

JP2

JP2

JP1

JP1

SHIELD

SHIELD

SHIELD

SHIELD

SHIELD

+

+

-

-

TB2

6

5

4

3

2

1

SHIELD

TO

EARTH

+

+

+

-

-

-

TB2

6

5

4

3

2

1

SHIELD

TO

EARTH

from both system circuits and earth
ground and that the shields are connected
together using terminal 5 of TB-2.

3. Using the ICP-B6 as a 70 Volt Speaker

Zone

When the ICP-B6 is used as a speaker zone,
the 24 VDC provides the supervision. If the 24
volts is lost or there is an open or shorted
speaker output line, the trouble condition
INPUT DEVICE RESPONSE TOO LOW
displays at the MXL/MXLV and the related
zone LED on the VSM-1 lights.

The 70.7V RMS audio input comes from the
amplifier via the ASC-2 Amplifier Supervision
card. The ASC-2 supervises the audio con-
nection path to the ICP-B6 and provides up to
100 watts of power. The ASC-2 can be used
as Style Y (Class B) or Style Z (Class A). Refer
to the ASC-2 Instructions, P/N 315-092085.

When the ICP-B6 is used as a speaker zone,
the output speaker lines are supervised and
power limited. The audio output cannot exceed

Содержание ICP-B6

Страница 1: ... can be used as an independent remotely located telephone zone a speaker zone 25V or 70 7V RMS or notification appliance circuit NAC depending on how it is configured It communicates through the analog loop of the MXL MXLV System OPERATION Up to 12 ICP B6s can connect to each analog loop of the MXL MXLV These modules must be connected to the first 12 address locations on the analog loop The 24 VDC...

Страница 2: ... 67 2 33 2 00 1 67 1 00 1 2 93 2 83 2 67 2 50 2 33 2 00 5 2 96 2 92 2 83 2 75 2 67 2 50 MAXIMUM LOOP RESISTANCE FOR EACH ICP B6 ON RISER NOTES 1 Resistances specified are for both wires 2 If higher currents are required Siemens Industry Inc recommends using a local auxiliary supply which is UL listed for fire protection signaling use The supply should be rated between 24 and 27 3 VDC When used as ...

Страница 3: ...ILTERED FULL WAVE RECTIFIED 1 5A POWER LIMITED ICP B6 ICP B6 PROGRAM PLUG PROGRAM PLUG TB2 TB1 TB1 6 6 6 5 5 5 4 4 4 3 3 3 2 2 2 1 1 1 ANALOG LOOP CONNECTION SUPERVISED MODULE INPUT SUPPLY FROM PS 35 PSR 1 OR UL LISTED POWER SUPPLY MANUFACTURED BY ALARM SAF Model BN4 002 UL ELECTRICAL INPUT DC SUPPLY SUPERVISORY OUTPUT ACTIVATED JP2 JP2 JP1 JP1 EARTH SHIELD TB2 6 5 4 3 2 1 EARTH SHIELD Figure 1 An...

Страница 4: ...4 Figure 4 ICP B6 Connections Using PSR 1 Figure 3 ICP B6 Connections When Using TRI 60 B6 ...

Страница 5: ...AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION RISER NOMINAL VOLTAGE MAXIMUM CURRENT 17 5 VDC 175 mA 10K 1 2W 5 EOL RESISTOR P N 140 112172 AT LAST FJ 303 5 6K 1 2W 5 EOL RESISTOR ELECTRICAL INPUT DC SUPPLY SUPERVISORY OUTPUT ACTIVATED OUTPUT 20 5 TO 30 VDC 18mA MAX 8V 8mA 11V 70mA SUPERVISED POWER LIMITED FROM MXL MMB OR ALD 2I ON MOM 4 12 MAX ICP B6 MODULES PER LOOP SUPERVISED NOTES 1 TH...

Страница 6: ...o input comes from the amplifier via the ASC 2 Amplifier Supervision card The ASC 2 supervises the audio con nection path to the ICP B6 and provides up to 100 watts of power The ASC 2 can be used as Style Y Class B or Style Z Class A Refer to the ASC 2 Instructions P N 315 092085 When the ICP B6 is used as a speaker zone the output speaker lines are supervised and power limited The audio output ca...

Страница 7: ...ARTH TB2 6 5 4 3 2 1 SHIELD EARTH TB2 6 5 4 3 2 1 SHIELD EARTH ASC 2 ASC 2 15K 1 2W 5 EOL RESISTOR P N 140 820400 15K 1 2W 5 EOL RESISTOR P N 140 820400 15K 1 2W 5 EOL RESISTOR P N 140 820400 STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 9 VDC 0 5 mA ACTIVATED 25 VRMS 35 W MAX STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 9 VDC 0 5 mA ACTIVATED 25 VRMS 35 W MAX 16 16 17 17 18 18 19 19 24K 1 ...

Страница 8: ...e plate to the box Figure 10 Mounting the ICP B6 NOTE When using the double gang switchbox or the plaster ring extension use the same four screws to fasten both the mod ule and the blank plate user supplied 3 Cover the module front plate with a 4 inch blank plate user supplied and fasten with two plate screws P N 315 095306 10 Siemens Industry Inc Building Technologies Division Florham Park NJ Sie...

Отзывы: