Siemens HCP Скачать руководство пользователя страница 5

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-034860-13

5

*REFER TO PAD-4 INSTALLATION INSTRUCTIONS, P/N 315-050217, FOR PROPER SETTING OF SWITCH 4. THE AUXILIARY POWER OUTPUT MUST BE CONFIGURED TO “ALWAYS ON”.

ALL WIRING MUST COMPLY WITH NATIONAL AND LOCAL CODES.

POSITIVE AND NEGATIVE 

GROUND FAULT 

DETECTED AT 

<500 OHMS FOR 

TERMINALS 3-6 ON TB1.

HCP MODULE IS USED FOR

NAC SUPERVISION AND ACTIVATION

FROM 

DLC/FS-DLC

DEVICE LOOP

LINE 1

LINE 2

EARTH

HCP

HCP

HCP MODULE IS USED FOR

NAC SUPERVISION AND ACTIVATION

SHIELD

EARTH

24 VDC
NAC UNITS
SEE P/N 315-096363

24K, W

½

,  5% 

EOL RESISTOR
P/N 140-034677

SHIELD

STYLE Y

SUPERVISED STROBE ACTIVATION “SPECIAL APPLICATION”

 SUPV: 1mA

ACTIVATED: 1.5A MAX

18.8V-28.2V FILTERED FULL WAVE RECTIFIED

POLARITY SHOWN IN ACTIVE STATE

STYLE Z

24K, W, 

5% 

½

EOL RESISTOR
P/N 140-034677

DC INPUT RATED

18.8-28.2VDC

SUPV:  30mA

ACTIVATED:  1.5A MAX

6 5 4 3 2 1

6 5 4 3 2 1

1 2 3 4 5 6

1 2 3 4 5 6

PROGRAMMING

POINTS

PROGRAMMING

POINTS

DC INPUT: 18.8-28.2VDC FILTERED FULL WAVE

MODULE INPUT SUPPLY:

XLS: PSC-12 (TB3) or PSX-12 (TB3).

FS-250: FS-250 NAC Circuit.

XLS/FS-250: PAD-4* (TB16), FC2025/2050,

FV2025/2050, FC922/924, FV922/924,

FCI2016/2017-U1 PERIPHERY BOARD AUX  

 POWER OR UL LISTED REGULATED 24 VDC 

POWER SUPPLY (POWER LIMITED).

HCP As Telephone Zone

When the HCP is used as a telephone zone module (FireFinder-XLS System only) as
shown in Figure 5, the 24 VDC provides power to the supervision and call-in detection
circuitry. If the 24 VDC is lost, a trouble condition displays on the PMI/PMI-2 of the
FireFinder-XLS.

The HCP provides a dial tone when a Fireman’s Master telephone (FMT) is taken off
hook or when a Portable FireFighter’s telephone (PFT) is jacked in.

Each HCP can support a maximum of 5 phones off hook. Throughout the system, no

more than 10 phones may be off hook at any one time.

The supervised telephone common talk riser starts at the TZC-8B module in the CAB
backbox. The common talk riser connects continuously to each HCP with a 10K end
of line device at the last HCP.  Tie the shield of these riser wires together using
terminal 5 of TB2 and isolate them from the system circuits and the earth ground.

Individual phones may not be connected to a riser that is wired to HCPs. The TZC-8B

zone must be configured for Riser usage in Zeus.

Connect the supervised telephone zone wiring to the HCP with twisted pair cable.
Terminate at the last station with a 75K ohm end of line resistor. As with the com-
mon talk line described in the paragraph above, be sure that the shield is continuous
and isolated from both system circuits and earth ground and that the shields are
connected together using terminal 5 of TB-2.

Figure 5

HCP Used As An NAC Module

The input power and NAC power inputs on TB2 (1-4)

must be connected to the same source.

All HCPs connected to a given DLC/FS-DLC circuit

must reside within a single notification zone.

Содержание HCP

Страница 1: ... module The HCP may only be assigned addresses 1 to 60 It is recommended to program the HCP devices first to ensure that enough addresses have been reserved for them Other devices may then be assigned to addresses in this range that were not assigned to an HCP Disconnect wire at terminal 1 and 2 on TB1 before programming To set the HCP device address Plug the programming cable of the DPU Programme...

Страница 2: ...er XLS FS 250 Desigo FC2025 2050 FV2025 2050 Cerberus PRO FC922 924 FV922 924 Systems through its addressable device loops These loops are connected to the DLC via terminal blocks on the CC 5 or CC 2 cardcage XLS or to the FS DLC viaTB3 on the FS MB FS MB2 main board FS 250 They may be wired Class A Style 6 or Class B Style 4 Figure 2 shows both wiring types and the connections to the DLC See the ...

Страница 3: ... HCP TB1 1 2 HCP TB1 1 2 ZONE 1 ZONE 2 DLC LOCATED IN ONE SLOT OF CC 5 CC 2 HCP TB1 1 2 HCP TB1 1 2 4 3 2 1 CLASS A WIRING CLASS B WIRING HCP TB1 1 2 HCP TB1 1 2 HCP TB1 1 2 HCP TB1 1 2 1 1 2 2 X1401 X1402 X1801 X1802 4 3 2 1 1 1 2 2 Detector circuits on periphery board for FC922 FV922 FC2025 FV2025 X1401 X1402 X1801 X1802 Figure 2 FireFinder XLS Device Loop Connections NOTES 1 Loop resistance 50 ...

Страница 4: ... FireFinder XLS FS 250 System control panel the Desigo FC2025 2050 FV2025 2050 Operating Unit and the Cerberus PRO FC922 924 FV922 924 Operating Unit For FS 250 Systems the NAC circuit must be set to always on in the panel or FS CT2 configuration tool See the Line Resistance table below for the allowable line resistance for each HCP output circuit E C N A T S I S E R E N I L T I U C R I C T U P T ...

Страница 5: ...XLS System only as shown in Figure 5 the 24 VDC provides power to the supervision and call in detection circuitry If the 24 VDC is lost a trouble condition displays on the PMI PMI 2 of the FireFinder XLS The HCP provides a dial tone when a Fireman s Master telephone FMT is taken off hook or when a Portable FireFighter s telephone PFT is jacked in Each HCP can support a maximum of 5 phones off hook...

Страница 6: ...RAMMING POINTS PROGRAMMING POINTS REFER TO PAD 4 INSTALLATION INSTRUCTIONS P N 315 050217 FOR PROPER SETTING OF SWITCH 4 THE AUXILIARY POWER OUTPUT MUST BE CONFIGURED TO ALWAYS ON Figure 6 HCP Used As A Telephone Zone HCP As 70 7V 25V Speaker Zone in an XLSV System When the HCP is used as a speaker zone FireFinder XLS System only the 24 VDC provides power to the supervision circuitry If the 24 vol...

Страница 7: ...ker zone wire length for various wire gauge sizes is shown in Figure 7 for the 70 7V option and in Figure 8 for the 25V option Connect the speaker output as Style Z Class A or StyleY Class B as shown in Figures 10 and 11 100 0 0 05 0 10 0 15 0 20 0 25 200 300 400 500 600 TOTAL SPEAKER ZONE WIRE LENGTH FEET dB LOSS 700 800 900 1000 SPEAKER LOAD 25 WATTS AT 70 7V RMS LOCATED AT END OF RUN DOES NOT I...

Страница 8: ...IO OUTPUT 70 7 25 VRMS 40 WATTS MAX POWER LIMITED STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5...

Страница 9: ...TS MAX POWER LIMITED STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5 EOL RESISTOR P N 140 034677 ...

Страница 10: ...ISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 14 VDC 1mA ACTIVATED 70 7 V 25V RMS 25 WATTS MAX CAPACITOR COUPLED 70 7V 25V RMS SPEAKERS 24K W 5 EOL RESISTOR P N 140 034677 EARTH SHIELD HCP 24K W 5 EOL RESISTOR P N 140 034677 68K 1 4W 5 EOL RESISTOR ON LAST HCP...

Страница 11: ...h deep plaster ring extension 2 Connect the field wiring 3 Insert the HCP into the box and fasten the device plate to the box 4 Cover the device front plate with the 5 inch switchplate supplied and fasten with two plate screws 4 INCH SQUARE BOX 2 1 8 INCHES DEEP DOUBLE GANG BOX 3 1 2 INCHES DEEP HCP HCP SWITCHPLATE 5 INCHES SQUARE SUPPLIED SWITCHPLATE 5 INCHES SQUARE SUPPLIED 1 1 2 INCH DEEP EXTEN...

Страница 12: ...security concept that is customized to individual security needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components us...