009197_h_--_--
Fire Safety
2016-04-20
en
Safety notes
Danger of damage to persons and
property
Please adhere to the following safety
instructions:
l
The installation is intended for stationary mounting
and dry rooms only.
l
Work on electrical installations must always be
performed by a qualified and authorized electrician
l
All feed lines must be inserted from the top or
through the rear panel.
l
The enclosed batteries may only be installed in the
housing by an authorized service technician.
l
If the station is mounted on a flammable wall, all
cut-out sections for the mounting holes must be
sealed using the supplied aluminum patch tabs.
Mounting notes
l
Any unevenness of the mounting surface
exceeding 5 mm must be equalized.
l
Wall mounting is done with screws Ø 6 mm
(enclosed in the delivery).
l
Rectangular cable entries must be provided with
edge protection strips.
l
At maximum 8 cables can be inserted per round
cable entry (20 mm with rubber grommet).
l
Only one cable may be inserted through each
screwed cable gland (not included in the scope of
delivery).
Hardware damage
The operating unit and components must
always be assembled by an authorized
service technician.
Mounting
1.
Break out the desired cable entries (2), (3) or (4) on
the housing.
2.
Mark the drillings (1) for the dowel holes by means
of the enclosed template.
3.
Drill the holes and place the dowels (enclosed in the
delivery).
4.
Fix the housing with the screws (enclosed in the
delivery).
5.
Stick the supplied aluminum patch tabs over all cut-
out sections for the mounting holes.
Danger of damage to persons and
property
Cables must always be inserted and
connected by a qualified service technician.
6.
Protect the electronic parts with the package cover
or other suitable means.
Reference documents
Documentation relating to further work sequences,
Document ID: 008851 Installation