9 Technical data

Supply

Operating voltage

DC 24 V

Standby power consumption

95 mA @24 V

Built-in power consumption, supply via
MoNetBus or AUX power

Max. 380 mA @ 24 V

Power consumption via PoE

Max. 185 mA @ 24 V

Ethernet interfaces

Sockets

4x RJ45, 10/100 Mbit/s

Length of line

P4, P5 'Local', limited to same
housing but must be min. 2 m

P2, P3 'Field', limited to same room
but must be min. 2 m, max. 6 m

Connectors

External supply input

4-pin plug-in terminal

Fault terminal

4-pin plug-in terminal

Fault output 'F1', 'F2'

Dry contact relay (common)

Switching current max. 1 A, resistive

Switching voltage max. DC 30 V

MoNetBus

22-pin flat-cable connector

External Ethernet connections 'P2', 'P3'

Additional voltage surge protection

Increased EMC protection

Ground fault supervision

Circuits

All connections are power limited

All connections – except local and
MoNet connections – are supervised

Module connections
(optional)

Ethernet module (electric) VN2001

RJ45 connection (TP), cable length max.
330 ft/100 m

Ethernet module (MM) VN2002

LC connector, multi-mode fiber optic

Fiber length 62.5/125°µm:
13123 ft/4 km with an 11 dB loss 

1

Fiber length 50/125°µm: 6561 ft/2 km
with a 7.5 dB loss 

1

Ethernet module (SM) VN2003

LC connector, single-mode fiber optic:

Fiber length 9/125°µm:
131233 ft/40 km with a 29 dB loss 

1

Mechanical data

Dimensions (W x H x D), with cover,
without optional modules

165 x 121 x 43 mm

Weight

560 g/1.2 lbs

Ambient conditions

For indoor use in dry rooms only

Operating temperature

120+/-3°F to 32+/-3°F

Rel. humidity during operation

93+/-2% at a temperature of 90+/-3°F

Protection category

IP30

1

 The length is a guide value dependent upon the loss of the cable used, the loss of the

connector types used, and the transmission losses that are present. The
corresponding values must be taken from the respective data sheets.

Technical data

9

A6V10407862_e_en_--

29 | 32

Содержание FN2012-A1

Страница 1: ...FN2012 A1 Ethernet switch modular Installation Mounting A6V10407862_e_en_ Smart Infrastructure 2019 11 25 ...

Страница 2: ...xpress authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Smart Infrastructure 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www sbt siemens com FIS Edition 2019 11 25 Document ID A6V10407862_e_en_ A5Q00060099 Siemens Industry ...

Страница 3: ...t modules 9 3 Views 11 4 Wiring 13 4 1 Wiring overview 13 4 2 General wiring FS20 FS920 14 4 3 General wiring XLS 15 4 4 MoNet bus connection 15 4 5 Ethernet switch in the Ethernet network 16 4 6 Ethernet switch as a repeater 18 5 Jumper settings on the VN2001 20 6 Pin assignments 22 6 1 POWER connector strip 22 6 2 FAULT connector strip 22 7 Indicators 24 8 Adjustment elements 27 9 Technical data...

Страница 4: ...4 32 A6V10407862_e_en_ ...

Страница 5: ...for optional Ethernet modules Depending on the application the Ethernet switch is supplied via a 24 V input via PoE using the Ethernet module electric or via the connection module MoNet FCA2031 Intended use Integrated switch for Ethernet backbone in FS20 FS920 and XLS fire detection systems VoIP switch for Integrated Voice Integrated voice switch Operation as an Ethernet repeater Remote switch for...

Страница 6: ...ional Ethernet module electric Via MoNet bus 2x slots for optional Ethernet modules ring ports not included in scope of supply VN2001 Ethernet module electric for distances up to 330 ft 100 m VN2002 Ethernet module MM optical Ethernet module for distances up to 13123 ft 4 km with an 11 dBm loss 1 VN2003 Ethernet module SM optical Ethernet module for distances up to 131233 ft 40 km with a 29 dBm lo...

Страница 7: ...lation in a fire control panel in the housing 2HU If the Ethernet switch modular is used as a repeater it is installed as a separate component in an external housing 1HU Figure 1 Installing the Ethernet switch modular in housings 2HU 1 Housing back box 2 Ethernet switch modular with Ethernet modules installed Installation Installation in FS20 FS920 housing 2 A6V10407862_e_en_ 7 32 ...

Страница 8: ...LS housings 1 2 Figure 2 Installing the Ethernet switch modular in XLS housings 1 Housing back box 2 Ethernet switch modular with Ethernet modules installed 3 3x fixing screw 4 Fixing slot in side tab 5 Threaded standoffs on back box 1 Position the Ethernet switch 2 as shown 2 Inserting the 3 fastening screws 3 into the side tabs 4 and screw the Ethernet switch 2 to the threaded sleeves 5 in the b...

Страница 9: ...odule in the FN2012 1 Ethernet switch modular FN2012 2 Ethernet module installed 3 Fastening screw with retention spring 4 Ethernet module 5 Plug contacts 6 Threaded hole for fastening 7 Positioning aid Before the Ethernet module electric VN2001 is installed the jumper settings must be plugged in as appropriate for how the module will be used Installation Installation of the Ethernet modules 2 A6V...

Страница 10: ... plug connector 3 Make sure that the Ethernet module 4 slots into the positioning aids 7 4 Use the fastening screw 3 to fix the Ethernet module in the threaded hole 6 5 Wire up the Ethernet module according to the wiring information provided below See also 2 Jumper settings on the VN2001 20 Installation Installation of the Ethernet modules 2 10 32 A6V10407862_e_en_ ...

Страница 11: ...r fault output F3 F4 not connected MoNetBus Knock out sheet cover on the X201 connector strip for the MoNet bus flat cable LEDs RM Redundancy manager indicator redundancy master FAULT General fault PWR Normal operation hardware ready for operation PD Not connected Switches and keys CONFIG S302 rotary switch with 16 positions for pre configured operating modes RESET S301 RESET key with three functi...

Страница 12: ...g or the same room up to a maximum length of 20 ft 6 m P2 External Ethernet connection 2 FIELD limited to the same housing or the same room up to a maximum length of 20 ft 6 m Figure 6 View of option slots not in use FN2012 Key for the option slots Element Des Function Connector P0 RING port 0 socket X1 for the optional Ethernet module optical or electric P1 RING port 1 socket X2 for the optional ...

Страница 13: ...own are current limited and supervised Connector Designation Description P0 P1 For FS20 FS920 applications Optional modules for Ethernet ring connections for electrical or fiber optic wiring TP SM MM For XLS applications Optional modules for Ethernet ring connections for optical wiring only SM MM P4 P5 Panel internal Ethernet connections P2 P3 External Ethernet connections e g for Desigo Fire Safe...

Страница 14: ...ternal Ethernet connections P2 and P3 are limited to the same room and have a maximum length of 20 ft 6 m The internal Ethernet connections P4 and P5 are limited to the same housing 4 2 General wiring FS20 FS920 Figure 8 View of cable routing Supply and battery connection The wiring must be routed as far away as possible from the installed components and the non current limited cables and fixed in...

Страница 15: ...the Ethernet switch modular and the PMI 2 connection J11 4 4 MoNet bus connection Preparing the Ethernet switch modular for MoNet bus connection Figure 10 Breaking out the MoNet bus cover plate l Use a screwdriver to carefully remove the cover plate for the MoNet connector as shown in the illustration a Levering the screwdriver in the direction shown by the arrow causes the cover plate to come loo...

Страница 16: ...P4 P5 P0 P1 POWER FAULT MoNet Ethernet Switch2 P2 P3 P4 P5 P0 P1 POWER FAULT MoNet MoNet PMI Mainboard Ethernet Panel Switch xx P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Optical or electrical Ethernet Ring MMS 24V supply MoNet PMI Mainboard Ethernet Panel P2 P3 P4 P5 P0 P1 POWER FAULT MoNet SAFEDLINK MoNet PMI Mainboard Ethernet Panel P2 P3 P4 P5 P0 P1 POWER FAULT MoNet SAFEDLINK Switch3 Switch4 Figure ...

Страница 17: ...detection Ring wiring with Ethernet module electric VN2001 Switch1 P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Switch2 P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Switch5 P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Electrical Ethernet Ring P2 P3 P4 P5 P0 P1 POWER FAULT MoNet P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Switch3 Switch4 P0 P1 P0 P1 P0 P1 P0 P1 P0 P1 Figure 13 Example of ring wiring with electrical Ethernet simplifi...

Страница 18: ...pers into slots P0 and P1 on the corresponding Ethernet module electric One repeater MoNet PMI Mainboard Ethernet P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Panel P2 P3 P4 P5 P0 P1 POWER FAULT MoNet MoNet PMI Mainboard Ethernet P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Panel Electrical Ethernet Repeater Switch1 Switch2 100 m 330 100 m 330 PoE ground fault Ground fault P0 P1 P0 P1 P0 P1 Figure 14 1x Ethernet sw...

Страница 19: ...with two repeaters Switch repeater VN2001 in port P1 VN2001 in port P0 Switch 1 Not connected PoE Repeater 1 PoE Ground fault supervision Repeater 2 Neutral position PoE Switch 2 PoE Not connected Guidelines Max two repeaters between two nodes Electric Ethernet distance between two nodes maximum 300 ft 100 m Repeater power supply via Power over Ethernet PoE from the VN2001 For each switch node 1 r...

Страница 20: ...he different settings for the corresponding function X102 1 24V RxT GND 24V TxT GND 1 8 X102 Figure 16 View of VN2001 with jumper strip X102 jumper strip Jumper setting on X102 Function 1 2 3 4 5 6 7 8 Ground fault supervision activated 1 2 3 4 5 6 7 8 PoE activated 1 2 3 4 5 6 7 8 Neutral position function deactivated Jumper settings on the VN2001 5 20 32 A6V10407862_e_en_ ...

Страница 21: ...Jumper setting on X102 Function 1 2 3 4 5 6 7 8 PoE for cables crossed at one end Jumper settings on the VN2001 5 A6V10407862_e_en_ 21 32 ...

Страница 22: ... Plug Connector FN2012 Supply input 6 2 FAULT connector strip The fault output is a dry contact relay and depending on the configuration it can be used to report fault states by means of contact interruption When the FN2012 is switched off the relay contact is deactivated opened The following fault messages can be configured via the web interface Fatal fault Ethernet switch modular malfunction Rin...

Страница 23: ...Admissible cable cross section AWG 24 AWG 12 0 2 2 5 mm F1 F2 F3 F4 FAULT Terminal Plug Connector Cover cap open F4 F3 F2 F1 IN OUT Pin assignments POWER connector strip 6 A6V10407862_e_en_ 23 32 ...

Страница 24: ...5 750 875 1000 1125 1250 1500 1375 ms 1625 1750 1875 FW Update Running Ethernet switch is loading firmware t 0 125 250 375 500 625 750 875 1000 1125 1250 1500 1375 ms 1625 1750 1875 FW Update Failed FW update could not be completed network connection may have been interrupted t 0 125 250 375 500 625 750 875 1000 1125 1250 1500 1375 ms 1625 1750 1875 Checksum Failed Incorrect firmware checksum t 0 ...

Страница 25: ... acting as the manager but has not been configured to perform this role t 0 125 250 375 500 625 750 875 1000 1125 1250 1500 1375 ms 1625 1750 1875 Manager Ring open There is a break in the Ethernet ring at one or more locations t 0 125 250 375 500 625 750 875 1000 1125 1250 1500 1375 ms 1625 1750 1875 Claim Manager Ring open t 0 125 250 375 500 625 750 875 1000 1125 1250 1500 1375 ms 1625 1750 187...

Страница 26: ...hich are switched off show open ports Defective unplugged cable Double manager Adapt configuration Only one Ethernet switch is allowed to be configured as the ring manager Unidirectional Data Link Fault Check the cabling of all optical fiber sections Replace each Ethernet switch in turn until you identify the defective device Table 5 Troubleshooting Indicators 7 26 32 A6V10407862_e_en_ ...

Страница 27: ...h for device configuration the Ethernet switch can be set to predefined network addresses or operation modes To accept a new configuration the switch must be in a de energized state when the setting is made or a hardware reset must be performed afterward Switch position IP address operating mode Sub net mask operating mode 0 Configured via web interface or MoNet bus Factory setting 0 0 0 0 Configu...

Страница 28: ...Switch position IP address operating mode Sub net mask operating mode E Repeater mode Repeater mode F 192 168 200 4 255 255 255 0 Adjustment elements 8 28 32 A6V10407862_e_en_ ...

Страница 29: ...cept local and MoNet connections are supervised Module connections optional Ethernet module electric VN2001 RJ45 connection TP cable length max 330 ft 100 m Ethernet module MM VN2002 LC connector multi mode fiber optic Fiber length 62 5 125 µm 13123 ft 4 km with an 11 dB loss 1 Fiber length 50 125 µm 6561 ft 2 km with a 7 5 dB loss 1 Ethernet module SM VN2003 LC connector single mode fiber optic F...

Страница 30: ...ale connector loss 1 0 dB Transmission losses 0 5 dB Length optical budget 2x male connector loss transmission losses cable loss per km Length in km 11 dB 2 x 1 dB 0 5 dB 2 5 dB per km 3 4 km Length in ft 11 dB 2 x 1 dB 0 5 dB 2 5 dB 3280 ft 9842 ft Technical data 9 30 32 A6V10407862_e_en_ ...

Страница 31: ... accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause inte...

Страница 32: ...try Inc Smart Infrastructure 8 Fernwood Road Florham Park NJ 07932 1 973 593 2600 www sbt siemens com FIS A6V10407862_e_en_ Siemens Industry Inc 2015 Technical specifications and availability subject to change without notice ...

Отзывы: