Electric Ethernet with copper wiring via 10/100BaseT connections (RJ-45
connector) with a VN2001 module – max. 330 ft/100 m long
●
Optical Ethernet with a fiber-optic 100BaseFX connection in multi-mode version
with a VN2002 module – max. 13100 ft/4 km long
●
Optical Ethernet with a fiber-optic 100BaseFX connection in single-mode version
with a VN2003 module – max. 131000 ft/40 km long
The type of ring wiring between each switch is independent and can be selected at will.
A maximum of 32 switches are allowed for each Ethernet ring.
The switch built into an FS20 panel is supplied via the MoNetBus from the PMI &
mainboard. If the switch is built into another housing or device, it is supplied with power
via a 24 V current-limited and supervised power supply that has been approved for use
in fire detection.
Ring wiring with Ethernet module (electric) VN2001
Switch1
P2
P3
P4
P5
P0
P1
P
O
W
E
R
F
A
U
L
T
MoNet
Switch2
P2
P3
P4
P5
P0
P1
P
O
W
E
R
F
A
U
L
T
MoNet
Switch5
P2
P3
P4
P5
P0
P1
P
O
W
E
R
F
A
U
L
T
MoNet
Electrical Ethernet Ring
P2
P3
P4
P5
P0
P1
P
O
W
E
R
F
A
U
L
T
Mo
Ne
t
P2
P3
P4
P5
P0
P1
P
O
W
E
R
F
A
U
L
T
Mo
Ne
t
Switch3
Switch4
P0
P1
P0
P1
P0
P1
P0
P1
P0
P1
Figure 13: Example of ring wiring with electrical Ethernet (simplified representation)
Jumper settings on the VN2001 for electrical Ethernet:
Switch
VN2001 in port P0
VN2001 in port P1
1
open
Ground fault supervision
2
open
Ground fault supervision
3
open
Ground fault supervision
4
open
Ground fault supervision
5
open
Ground fault supervision
The minimum cable length for an electrical 10/100BaseT cable on the VN2001 is
10 ft/3 m. Shorter lengths are only permitted within the same housing, or if the
connection does not need to be supervised in accordance with the UL864 standard.
Wiring
Ethernet switch in the Ethernet network
4
A6V10407862_e_en_--
17 | 32