10
Operating unit with PMI & mainboard FCM2004
Technical data
82
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
After the firmware has been updated and before the restart, S38-2 must be in the
'OFF' position, otherwise the firmware is updated again.
S38-1 has an impact on starting the operation system.
Position S38-1
Function
ON
Station is started in Restore factory settings mode.
OFF
Station is started normally.
After the factory settings have been restored and before the restart, S38-1 must
be in the 'OFF' position, otherwise Restore factory settings mode is triggered
again.
S33: Switch for ground fault monitoring of the Ethernet connection
Both switches must be in the same position.
S33-1
S33-2
Function
ON
ON
Ground fault monitoring switched on
OFF
OFF
Ground fault monitoring switched off
OFF
ON
Not admissible
ON
OFF
Not admissible
10.5
Technical data
Supply input
Voltage
DC 20…30 V
Quiescent current (display illumination off)
120 mA
Maximum current (display illumination on and
lamp test on)
200 mA
Display
Dimensions (L x W)
115 x 50 mm
Resolution
256 x 112 pixels
Interfaces
Slots for serial options (RS232 or RS485
module)
For RS232 module for event printer
For RS485 module for ESPA-4.4.4
interface, FAT, FBF, UGA or remote
EVAC-NL operation
Slots for network modules (SAFEDLINK)
Full functionality (incl. degraded mode
function)
Degraded mode function only
Ethernet connection
10/100 Mbit/s
Connections for peripheral data bus
1
Connections
Ethernet
RJ45
Peripheral data bus
Plug-type connection
Mechanical data
Dimensions (W x H x D)
427 x 200 x 25 mm
Weight
1800 g