Technical data
11
Building Technologies
Fire Safety & Security Products
11.2008
4.2
Connection to transponder FDCC221 (integrated in FDV241)
Connections
Design: plug-type connection
Cross-section: 0.2 – 1.5 mm
2
Operating voltage
12 – 33 V DC
Operating current (closed circuit)
0.6 – 0.75 mA
Operating temperature
-10 to +55 °C,
Relative humidity
≥
95 % rel. (at T = 25 ±3 °C)
93 % rel. (at T = 40 ±2 °C)
temporary condensation permissible
Maximum current connection factor
3
Quiescent current connection factor
3
Address connection factor
1
Separator connection factor
1
Protocol FDnet
Compatibility
For details see doc. no. 008331 'List of compatibility'
External alarm indicator
Connector for external alarm indicator
None
Standards
CPD EN
54-17
EN 54-18
VdS approvals
G208063