Planning
Technical CO alarm
4
59 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
4.3.4 Application examples
You will find application recommendations such as the selection of the detector
settings for the various applications in document 010030.
The table below includes examples regarding the selection of the parameter set for
CO for the point detector. The examples cannot be used universally, but illustrate
typical applications.
Environment
Detection behavior wanted
Parameter set for CO
Rooms with open fire
Very fast response needed
'Static 40 (4)'
Heating rooms
Evaluation of time dependency of CO
concentration
'Balanced EU2 (1)' or
'Balanced US1 (7)'
Combustion or fermentation plants
Very robust behavior towards deceptive
phenomena
'Robust EU1 (0)'
Car parks, automotive workshops
Robust behavior towards deceptive
phenomena
'Balanced EU2 (1)' or
'Balanced US1 (7)'
Underpasses and escape compartments
Evaluation of time dependency of CO
concentration
'Balanced EU2 (1)' or
'Balanced US1 (7)'
Animal stalls
Fast reaction required
'Static 50 (5)'
Chemical labs or production sites
Fast and very sensitive reaction required
'Static 40 (4)'
Alternatively 'Balanced EU2 (1)'