4.2.1.3 Specification
The following table displays the properties and fields of application of the
parameter sets of radio fire detector FDOOT271-O in sensor mode 0.
No.
Name
Optical
Thermal
Typ. Response
time
from - typ. - to
Sensitivity,
open fire
Sensitivity,
smoldering fire
Static
activation
temperature
Differential activation
temperature
1
Differential
activation
possible from:
[s]
[%/m]
[%/m]
[°C]
∆T [K]
[°C]
0
Robust
80
3.2
11.4
80
29
30
2
Robust
80
3.2
11.4
80
29
30
5
Suppression
90 -160 - 760
3.2
11.4
80
29
30
6
Fast Response
20 - 30
1.6
5.6
80
25
3
1
Applicable with fast temperature increases >10 K/min.
The following table shows which product version ES meets which standard for the
parameter sets.
No.
Name
ES <8
ES ≥8
0
Robust
EN 54-7
EN 54-7, EN 54‑29
2
Robust
EN 54-7
EN 54-7, EN 54‑29
5
Suppression
EN 54-7
EN 54-7, EN 54‑29
6
Fast Response
EN 54-7
EN 54-7, EN 54‑29
Planning
Parameter sets for FDOOT271-O
4
28 | 50
A6V10425624_en--_h