4 Planning
The radio connection means that there is no need to wire the radio devices,
such as the radio fire detector, radio manual call point, etc., in the usual way.
Together with the radio gateway, the radio devices form a radio cell. The control
panel treats this radio cell as a loop or a stub. It is used for the 'Sinteso' and
'Cerberus PRO' product lines.
In the 'Planning' document (A6V10227631), you will find detailed information about
the components of the radio fire detection system as well as the necessary devices
and device combinations.
You will find more information in the 'List of compatibility'.
4.1 Compatibility FDnet/C-NET
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
FDnet
X
From MP5
–
–
–
C-NET
–
X
From IP5
–
–
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
4.2 Fields of application
The radio manual call points are intended for use in places where a fire can be
detected by people who can manually trigger an alarm.
4.3 Mounting site
The radio manual call points must be mounted in easily accessible places at a
height of 0.9...1.6 m on an even surface.
Observe the country-specific regulations for the exact mounting height!
4.4 Environmental influences
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand certain environmental
conditions.
The following factors must be taken into consideration:
●
Chemicals
●
Temperature
●
Moisture
Planning
Compatibility FDnet/C-NET
4
A6V10401120_g_en_--
25 | 46