CANopen add-on module
SFIDK.PS.023.A2.02
20
7. SDOs (Service Data Objects)
System control
Index
Object name
Description
2810h
System control
Containing control sets to control the
flowmeter
Sub
Name
Access
Type
PDO
Description
index
mapping
0
No. of Entries
R
U8
No
2
1
Control Set 1
W
U8
Yes
See description below
2
Control Set 2
W
U8
Yes
See description below
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
T2HR_MASK T2HR_CMD
T1HR_MASK
T1HR_CMD
T2R_MASK
T2R_CMD
T1R_MASK
T1R_CMD
Name
Description
T2HR_MASK
0: T2HR_CMD is disabled
1: T2HR_CMD is enabled
T2HR_CMD
0: Totalizer 2 is in RUN mode (normal operation)
1: Totalizer 2 is in HOLD mode
T1HR_MASK
0: T1HR_CMD is disabled
1: T1HR_CMD is enabled
T1HR_CMD
0: Totalizer 1 is in RUN mode (normal operation)
1: Totalizer 1 is in HOLD mode
T2R_MASK
0: T2R_CMD is disabled
1: T2R_CMD is enabled
T2R_CMD
0: No action
1: Totalizer 2 is reset (reset takes place when T2R_CMD changes from 0 to 1)
T1R_MASK
0: T1R_CMD is disabled
1: T1R_CMD is enabled
T1R_CMD
0: No action
1: Totalizer 1 is reset (reset takes place when T1R_CMD changes from 0 to 1)
Control set 1
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
Reserved
Reserved
BAT_MASK
BAT_CMD
ZADJ_MASK
ZADJ_CMD
Name
Description
BAT_MASK
0: BAT_CMD is disabled
1: BAT_CMD is enabled
BAT_CMD
00: Batch STOP command
01: Batch START command
10: Batch PAUSE command
11: Batch RESUME command
ZADJ_MASK
0: ZADJ_CMD is disabled
1: ZADJ_CMD is enabled
ZADJ_CMD
0: No action
1: Start Zero Adjust. The zero adjustment may take a while to finish.
The application has full responsibility to keep track of this period
Control set 2