background image

2

Building Technologies

A6V10436766_b_en_--

Fire Safety

2014-11-27

Status” inputs and alarm” inputs

“Alarm“ inputs trigger an alarm as soon as the input is activated. “Status“ inputs trigger a
monitoring status change as soon as they are activated.

Line monitoring and circuitry

The input lines are monitored for open line or open line and short circuit. To make these
possible, resistors must be properly connected to the end of lines of the input (Fig. 1). When
an open line or a short circuit occurs on one of the input lines, a fault message is transmitted
to the control panel. The input must be potential-free.

Output

External power output (Default)

Normal operation (output lines monitored)

-

Be used for controlling (e.g. operating a horn/strobe).

-

The module switches the externally supplied 24 VDC voltage in active status on the

output.

-

In inactive status the output line is monitored for open line and short circuit (Fig. 3).

-

The jumper on the input/output module must be plugged onto J2 (Fig. 2)

Fig.2 Input/output module jumper position J2

Fig.3 Connection for normal operation with output line monitored for short circuit and open line

Configuration

The following configurations are possible through controller or configuration tool:

l

After activating the output remains:

Steady output

Pulse output: How long the contact remains active can be configured by controller or
configuration tools (pulse duration).

l

Failsafe behavior when the FD18-BUS detector line is current-free or in degraded mode.
The error behavior defines the position of the output in case of an error:

Off: Output remains in the same position as before the error

Activation: Output is activated in case of an error

Deactivation: Output is deactivated in case of an error

The controller does not monitor external equipment status (activated/inactivated).

Inverted operation (output lines not monitored)

-

Be used for controlling (e.g. closing a door).

-

The module switches the externally supplied 24 V DC voltage in active status on the

output.

-

In normal status there is no monitoring for open line and short circuit.

-

The jumper on the input/output module must be plugged onto J2 (Fig. 4).

1N5404

Содержание FDCIO181-1

Страница 1: ...ot activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Communication with controller via FD18 BUS detector line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application Input With the input a status can be monitored the input can be configured by controller or...

Страница 2: ...onto J2 Fig 2 Fig 2 Input output module jumper position J2 Fig 3 Connection for normal operation with output line monitored for short circuit and open line Configuration The following configurations are possible through controller or configuration tool l After activating the output remains Steady output Pulse output How long the contact remains active can be configured by controller or configurati...

Страница 3: ...put How long the contact remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activ...

Страница 4: ...activated in case of an error Deactivation Output is deactivated in case of an error The controller does not monitor external equipment status activated inactivated Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the states of the inputs outputs The cover of the printed ci...

Страница 5: ... surface with two screws Fig 10 Distance between holes 182 0 1 0mm 4 Insert the cables and fix the cables in the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installatio...

Страница 6: ...nt 0 51 mA Output Capacity Monitoring resistor Diode 2 A 24 VDC 3 3k Ω 1 4w 1N5404 Input Monitoring resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Details...

Отзывы: