Note:
If the relays OUT1...OUT3 operate
external contactors, these must be fitted with
RC snubber circuits to manufacturer
specifications to prevent excessive switch-off
voltage peaks.
OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable
Resolution:
11 bit
Time constant of the D/A converter
T
90
:
50 ms
Limiting frequency of the continuous
controller:
> 2 Hz
Current output
0/4...20 mA, configurable.
Signal range:
0...approx. 21.5mA
Load :
≤
500
Ω
Load effect:
0.02%/100
Ω
Resolution:
≤
22
µ
A (0.1%)
Error:
≤
40
µ
A (0.2%)
Voltage output
0/2...10V configurable
Signal range:
0...11 V
Load:
≥
2 k
Ω
Load effect:
none
Resolution:
≤
11 mV (0.1%)
Error:
≤
20 mV (0.2%)
OUT3 used as transmitter supply
Output:
22 mA /
≥
13 V
OUT3 used as logic output
Load
≤
500
Ω
0/
≤
20 mA
Load > 500
Ω
0/> 13 V
OUTPUTS OUT5, OUT6
Galvanically isolated opto-coupler outputs.
Grounded load: common positive control
voltage.
Output rating: 18...32 VDC;
≤
70 mA
Internal voltage drop:
≤
1V with I
max
Protective circuit: built-in against short circuit,
overload, reversed polarity (free-wheel diode
for relay loads).
POWER SUPPLY
Depending on version:
AC SUPPLY
Voltage:
90...260 V AC
Frequency:
48...62 Hz
Power consumption: approx. 7.0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:
20,4...26,4 V AC
Frequency:
48...62 Hz
DC voltage:
18...31 V DC
Power consumption:
approx. 7 VA (W)
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters, and adjusted
set-points, control mode: non-volatile storage in
EEPROM
BLUEPORT
FRONT INTERFACE
Connection of PC via PC adapter (see
„Accessories“).
The BlueControl
software is
used to configure, set parameters, and operate
the KS 50-1
TCont
.
TECHNICAL DATA
Operating note KS 50-1
TCont
25
Slave telegram
Process value input INP1
Mains supply
SupplementaryinputINP2
Digital input di1
Relay outputs OUT1,2
RS485 /422 interface
TTY interface
Relay output OUT3
Digital inputs di2, 3
Universal output OUT3
Transmitter supply U
T
OUT5, OUT6
Safety isolation
Functional isolation
Galvanic isolations: