Commissioning and diagnostics
ECOFAST Motor Starters
4-2
GWA 4NEB 950 5221-12 DS 01
4.1
Process data and process images
Definition of process image
The process image is part of the system memory in the AS-i master. At the
start of the cyclical program, the signal states of the inputs are transferred
to the process image of the inputs. At the end of the cyclical program, the
process image of the outputs is transferred to the slave as a signal state
.
Table
The table below shows the process data and process images:
Table 4-1: Process data and process image, AS-Interface
Process data
Process image:
4 outputs, DO 0.0 to DO 0.3
4 inputs, DI 0.0 to DI 0.3
4 parameters, PO 0.0 to PO 0.3
Signal:
[1]: HIGH
[0]: LOW
Outputs
Control commands (PLC to motor starter)
DO
-
0.
0
Motor CW
[1]: ON
[0]: OFF
1
Motor CCW
[1]: ON
[0]: OFF
2
Brake
[1]: ON
[0]: OFF
3
Trip Reset
[
0] –> [1]: ACTIVE
[0], [1]: NOT ACTIVE
Inputs
Signals (motor starter to PLC)
DI- 0.
0
Ready (automatic)
[1]: YES
[0]: NO
1
Motor on
[1]: YES
[0]: NO
2
IN1 (input 1)
[1]: 24 V present
[0]: OPEN
3
IN2 (input 2)
[1]: 24 V present
[0]: OPEN
Parameters
Technology (PLC to motor starter)
PO- 0.
0
Reserved
1
Temperature sensor
[1]: Thermoclick
[0]: PTC type A
2
Behavior in the event of
overload - temperature sensor
[1]: Trip
[0]: Warn
3
Auto reset
[1]: NO
[0]: YES
0
1
Содержание Ecofast 3RK1 323-2AS54-1AA0
Страница 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Страница 2: ......
Страница 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Страница 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Страница 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Страница 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Страница 75: ......