Commissioning
Resetting the SMF6120 to delivery status
6
66 | 82
Building Technologies
009865_m_en_--
Fire Safety
2015-11-06
Figure 6: View inside radio base SMF6120
1 'New' log-on button
3 Status indicator
2 Battery plug connections
4 3.6 V lithium AA batteries
Procedure:
1. Unscrew the manual call point SMF121 from the radio base SMF6120.
2. Pull both plugs of the battery connection cable out of the printed circuit board in
the radio base.
3. Wait 10 seconds for the batteries to discharge.
4. Press the alarm button on the manual call point SMF121.
5. Plug both plugs of the battery connection cable back into of the printed circuit
board in the radio base.
a
The status indicator flashes three times repeatedly.
6. Press the 'New' log-on button in the radio base until the status indicator only
flashes once.
7. Reset the alarm button using the reset slider on the manual call point SMF121
and wait until the status indicator displays 'System search'.
a
The configuration data is deleted from the manual call point with radio base
SMF6120.
a
The manual call point with radio base is ready to log back on to a radio
gateway.
See also
2
Logging radio detectors on to the radio gateway [
1
4
3
2