background image

Vehicle Description

5

the test position.  The rollers on the arms strike vertical
angles on the cell wall and stop the breaker at the test
position.  If the breaker is to be operated at this position,
remove the crank and engage the secondary contacts in
the manner described in the section under Secondary Con-
tacts.  To move the breaker from the test position to the
fully engaged operating position, put the crank on the shaft,
push in and rotate to engage the levering-in coupling, and
crank clockwise.  The torque required will increase when
the primary contact fingers engage the stationary contact
studs in the cell.  Continue cranking to the end of the travel
where the interlock will again fall free, pushing the crank
back out.  Remove the crank.  The indicator on the panel
will again point to the word “OPERATE”.

To remove the breaker from the operating  position, first
check that the breaker is open.  The levering-in device can-
not be engaged unless the breaker contacts are open.  Put
the crank on the operating shaft, push in and rotate to en-
gage the coupling, and turn counterclockwise until the
breaker returns to the test position.  Remove the crank.
The breaker may now be operated at the test position or
rolled out of the cell.

Figure 2. Interlock Position Indicator

Interlock Position Indicator
The interlock position indicator (Figure 2) gives a positive
indication of the position of the breaker interlock.  It oper-
ates from  the levering-in device shaft.  When the indica-
tor points to the word OPERATE, the interlock is free and
the breaker may be closed or tripped.  When the indicator
points to the word INTERLOCKED, the interlock is func-
tioning and the breaker cannot be closed.  Since the inter-
lock is operative only when the breaker is in fan interme-
diate position between fully engaged and fully withdrawn,
it also serves as  a means of indicating that the breaker is
in the Operating Position and the main disconnecting con-
tacts fully engaged, or that it is in the Test Position with
the contacts separated.

Test Position
The breaker may be rolled into the metal clad cell until the
rollers on the levering-in device stop against a pair of ver-
tical angles welded into the cell.  The levering-in device is
not operated.  This is the test position in which the breaker
primary contacts are separated from the energized con-
tacts in the cell, and a metal shutter is closed completely
isolating all high voltage parts from the breaker.  The sec-
ondary contacts may be engaged and the breaker oper-
ated safely for test purposes without the arc chutes or bar-
rier.

Operating Position
The breaker may be moved from the test to the operating
position by engaging the levering-in device and rotating
the levering-in crank clockwise.  As the breaker travels
beyond the Test Position, the metal shutter covering the
high voltage primary contacts will be automatically opened
by the shutter rollers which are locate on each side of the
breaker frame at the rear (Figure 1a).  At the end of the
travel, all the breaker contacts are engaged.  This is the
Operating Position.

Interlock
The interlock on the DH breakers has two functions to per-
form.  First, it prevents the breaker from being moved from
the test to the operate position or vice versa with the con-
tacts closed.  Second, if the breaker is in some intermedi-
ate position between the test and operate positions, it pre-
vents the contacts from being closed.

This interlocking action is accomplished by having a rod,
operated by the breaker mechanism, and a pin operated
by the levering-in device, move at right angles to each
other.

Содержание DHR Series

Страница 1: ...Instructions Installation Operation Maintenance SGIM 9958B Vacuum Circuit Breakers Vehicle Type DHR 4 16kV to 15kV ...

Страница 2: ...rts should not be used in the repair of the equipment Follow all safety instructions contained herein IMPORTANT The information contained herein is general in nature and not intended for specific application purposes It does not relieve the user of responsibility to use sound practices in application installation operation and mainte nance of the equipment purchased Siemens reserves the right to m...

Страница 3: ... Breaker Module Into Compartment 4 Levering Device and Breaker Interlock 4 Levering in Device 4 Interlock Position Indicator 5 Test Position 5 Operating Position 5 Interlock 5 Secondary Contacts 6 Ground Contact 6 Mechanism Operated Control Switch 6 Maintenance 7 Introduction and Maintenance Intervals 7 Recommended Maintenance and Lubrication 7 Removal from Switchgear 8 Checks of the Primary Power...

Страница 4: ...ountered by the user These words are defined as Danger Indicates an imminently hazardous situation which if not avoided will result in death or serious in jury Warning Indicates a potentially hazardous situation which if not avoided could result in death or serious injury Caution indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Dangerous Proce...

Страница 5: ...e shipping pallet for later use if the breaker is to be stored prior to its installation 2 Inspect for concealed damage Notification to carrier must take place within 15 days to assure prompt reso lution of claims 3 Each circuit breaker should be appropriately lifted us ing lifting sling rated for at least 2 000 lbs Breaker shall be lifted by Upper B phase post insulator 4 The palleted circuit bre...

Страница 6: ...re is an arm on each side mounted on a com mon shaft across the back of the breaker On each arm is a roller which engages a groove in the sidewall of the cell A removable crank engages another shaft in the right front corner of the breaker which turns the arms through a worm gear and pinion arrangement Hazardous voltages and high speed moving parts Will cause death serious injury and property dama...

Страница 7: ...ce the inter lock is operative only when the breaker is in fan interme diate position between fully engaged and fully withdrawn it also serves as a means of indicating that the breaker is in the Operating Position and the main disconnecting con tacts fully engaged or that it is in the Test Position with the contacts separated Test Position The breaker may be rolled into the metal clad cell until t...

Страница 8: ...ures a good electrical contact The flexible control wires are soldered to each plug and are arranged in a loop to allow free movement of the contact slide Figure 3 Secondary Contacts Ground Contact A ground contact is located at the left rear of the breaker from directly above the 18 point secondary plug Figure 3 Six spring loaded floating contact fingers engage the ground contact at the rear of t...

Страница 9: ...sed on your experience with the equipment in the ac tual service environment Regardless of the length of the maintenance and lubrica tion interval Siemens recommends that circuit breakers and switchgear should be inspected and exercised annu ally Recommended Maintenance and Lubrication Periodic maintenance and lubrication should include all the tasks shown in Table 1 Recommended procedures for eac...

Страница 10: ... red Trip pushbutton again and observe the spring con dition indicator It should read Discharge Refer to Cir cuit Breaker Operator Manual SGIM 9918 5 Remove the breaker from the switchgear Refer to the preceding installation section of this manual for special instructions and precautions regarding removal of a breaker which is not at floor level Checks of the Primary Power Path The primary power p...

Страница 11: ...echanical damage burning or pitting Using a clean cloth saturated with denatured alcohol clean old lubricant from primary disconnects and apply Siemens contact lubricant reference 15 171 370 002 in a very thin layer Fastener Check Inspect all fasteners for tightness Both lock nuts and re taining rings are used Replace any fasteners that appear to have been frequently removed and replaced Racking M...

Страница 12: ...9958B 1 2003 Printed in U S A 2001 Siemens Power Transmission Distribution Inc SIEMENS is a registered trademark of Siemens AG Siemens Power Transmission Distribution Inc P O Box 29503 Raleigh NC 27626 0503 ...

Отзывы: