background image

4 / 10 

Siemens 

RXZ90.1 – Receiver with PPS2 interface 

CA2N1644en_05 

Building Technologies 

 

02.08.2010 

Mounting instructions 

 

The receiver is suitable for mounting on walls or ceilings, and for installation in a 
flush mounting box 

 

An elevated position, or mounting on the same storey as the room unit(s) can extend 
the wireless range 

 

Depending on the materials used for the ceiling, the receiver may be concealed in 
the ceiling void  
(note that metal must be avoided) 

 

The admissible ambient conditions must be observed 

 

The mounting instructions and a drilling template are printed on the device packa-
ging 

 

A set of fixing accessories is enclosed with the room unit 

 

 

Do not mount on a metal surface 

 

Do not install behind a cover or a metal grid which impedes wireless communication 

 

The unit must be mounted at least 1 metre from the transmitter 

 
 

Response on start-up (PPS2)

 

After an interrupt of the PPS2 interface the communication will only be re-established 
when the connected controller polls the PPS2 addresses. The duration of the 
corresponding cycle is: 
RXA: 10 sec; RXB, RXL and RXC: 3 min; PX: 30 sec. 
 
 

Commissioning and establishing wireless communication

 

Please do not make any adjustments without a careful reading of the following 
commissioning notes. 
 

 

The unit(s) must be mounted at least 1 metre from the receiver 

 

Where there is more than one receiver in the same building, communication must be 
established with each receiver separately, after a time delay. This is because 
commissioning signals can be received from adjacent rooms, or even from 
neighbouring buildings during the commissioning process.  

 

Communication between the wireless room unit and the receiver can be 

established

 

either before or after installation. 

Checking

 the wireless communication (see below) 

only makes sense when all the devices are mounted. 
 

PLEASE FOLLOW THE INSTRUCTIONS EXACTLY IN THE SEQUENCE SHOWN: 

1.  Snap-mount the RXZ90.1 receiver on the mounting plate (power ON: the receiver 

goes into "Installation" mode). 

2.  Insert batteries in all the allocated wireless room units (max. 5) or remove the 

isolating strip from the batteries already inserted. (power ON: the room unit 
transmits its unique ID to the receiver). 

3.  You can establish communication with the next receiver as soon as the 4-minute 

"Installation mode" has expired in all the room units. 

 

STOP

 

Caution! 

STOP

 

Caution! 

Establishing 
communication  
for the first time 

Содержание DESIGO RXZ90.1

Страница 1: ... use only in conjunction with the QAX90 1 QAX91 1 wireless room units data sheet CA2N1643 Determines the average room temperature from several room units PPS2 interface to controller may be changed to PPS Socket for commissioning and service tool diagnostic plug or service terminal Use The RXZ90 1 is used for wireless reception of the room temperature from the QAX90 1 and the room temperature setp...

Страница 2: ...ceiver determines the average of the temperature values received The average room temperature is then transmitted to the room controller In the case of room units with setpoint adjusters QAX91 1 only one may be assigned to each receiver Other room units with setpoint adjusters are treated as QAX90 1 units room temperature only QAX91 1 QAX90 1 QAX90 1 RXZ90 1 QAX90 1 QAX90 1 00481 A 868 MHz Design ...

Страница 3: ...municipal waste The relevant national legal rules are to be adhered to Regarding disposal use the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The receiver receives its power via the PPS2 interface Receiver range approx 30 m and up to 100 m in the open The range can vary widely Room topologies and building materials metal concrete etc reduce...

Страница 4: ...ec Commissioning and establishing wireless communication Please do not make any adjustments without a careful reading of the following commissioning notes The unit s must be mounted at least 1 metre from the receiver Where there is more than one receiver in the same building communication must be established with each receiver separately after a time delay This is because commissioning signals can...

Страница 5: ...e Insert batteries in the replacement unit s these will switch to installation mode The receiver recognises all newly connected room units and adds these to its device list Caution Wait 4 minutes before changing any further links Sustained pressure 5s on the button of one of the existing room units The receiver will delete this room unit from its device list and then switch to installation mode In...

Страница 6: ...is connected to the controller and its device list is empty With fewer than 5 room units registered connecting the diagnostic plug to the receiver and pressing the button briefly 1s Plugging the RXT20 1 service terminal into the receiver with an empty device list and pressing the service pin on the RXT20 1 4s Sustained pressure 5s on the button of an existing room unit The receiver will delete thi...

Страница 7: ...ause 4 room units 4 flashes 5 s pause 5 room units 5 flashes 5 s pause Normal mode Receiver s device list not empty and PPS2 communication not working Flashes more slowly approx once s e g during initialisation of the controller after POWER ON Status Green LED signals PPS2 power supply ON ON continuously PPS2 short circuit OFF Pushbutton Action Brief pressure 1s Sets receiver to installation mode ...

Страница 8: ...ingle cable length controller Room unit See Installation guidelines DESIGO RXC CA110334 DESIGO RXB RXL CM110891 DESIGO RXA CA2Z3884 DESIGO PX CA110396 2 core or 4 core twisted pairs unscreened Tool connecting cable Made up in house max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions Ambient conditions to IEC7...

Страница 9: ...S2 data negative Bus connection looped to tool socket C 3 with LONWORKS bus DESIGO RXC CLA C 4 with LONWORKS bus DESIGO RXC CLB 5 8 Not used Tool socket Standard RJ45 tool socket Communication Diagnostic plug 1 3206Z01 2 3 45 67 8 1 with LONWORKS bus DESIGO RXC CLA 2 with LONWORKS bus DESIGO RXC CLB 3 4 5 6 7 CP PPS2 data 8 CP PPS2 data Button for installation Button for installation Red LED Red L...

Страница 10: ...10 10 Siemens RXZ90 1 Receiver with PPS2 interface CA2N1644en_05 Building Technologies 02 08 2010 Dimensions 9 5 32 36 4 2 60 00496 90 100 56 60 56 2000 2010 Siemens Switzerland Ltd Subject to change ...

Отзывы: