background image

2/6 

Siemens 

QAX33.1 – Room unit with PPS2 interface 

CA2N1642en_02 

Building Technologies 

 

30 Jun 2009 

Ordering 

When ordering, please specify the quantity, product name and type code. 

Example: 

30 

Room units  

QAX33.1 

Equipment combinations 

The room unit is suitable for use in conjunction with all controllers which incorporate a 
PPS2 room unit interface (e.g. DESIGO RX, DESIGO PX). 

Mechanical design 

The room unit is designed for surface mounting (with knock-outs for cable entry from 
the top or bottom) or for mounting on a recessed conduit box with the cables connected 
from the rear. 

The unit comprises a housing and base unit, connected by releasable snap-fittings.  

The base unit accommodates the screw terminals which have an integrated terminal 
strip.  

The housing accommodates a printed circuit board, room temperature sensor element, 
setpoint adjuster, rocker switch for mode selection and fan speed selection, plug-in 
connectors and a socket for the commissioning and service tool or service terminal.  

Both the housing and base are made of plastic. 

 
 
 
 
 
 
Base unit 
 
 
Housing 

80082

 

 
 
 
 
 
 

80084

Socket for the commissioning 
and service tool or service 
terminal 

 

80168A

 

 
 
 
Dial for stepless adjustment of the setpoint 
 
 
 
LEDs to indicate control mode and fan speed 

Rocker switch for mode selection and fan speed 

 
The controller control mode can be selected on the basis of occupancy, using the 
rocker switch on the room unit. The same switch can also be used for manual selection 
of up to three fan speeds. 

Pressing once in the direction of the left arrow switches one stage to the left, and press-
ing once in the direction of the right arrow switches one stage to the right. The current 
control mode or the manually selected fan speed is indicated by LED. 

Operator controls  
and indication 

Rocker switch for selec-
tion of mode and fan 
speeds 

Содержание DESIGO RX QAX33.1

Страница 1: ...nit is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of a room controller The QAX33 1 is typi cally used in conjunction with a fan coil system for fan control It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This to...

Страница 2: ...perature sensor element setpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80168A Dial for stepless adjustment of the setpoint LEDs to indicate...

Страница 3: ...e the systems setup for collecting electronic waste Observe all local and applicable laws Engineering notes The device receives its power from the connected controller via the PPS2 interface extra low voltage Only one room unit may be connected to a RX room controller A maximum of 5 room units may be connected to a PXC automation station they are identified by different settings of their address p...

Страница 4: ...ge range SELV PELV DC 12 15 V The room unit receives its power from the connected controller via the PPS2 interface Power consumption from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accur...

Страница 5: ...Dimensions Color Housing front dial NCS S 0502 G RAL 9003 signal white Housing base unit rocker switch RAL 7035 light grey Weight Excluding packaging 0 12 kg Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool s...

Страница 6: ... RXC room controller 1741A03 PPS2 Tool A R1 B 7 8 1 2 4 3 2 1 C C CP CP N1 CP CP CLA CLB PPS2 LonWorks Bus Twisted pair R1 Room unit QAX33 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Отзывы: