![Siemens Desigo PXC4.E16 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/siemens/desigo-pxc4-e16/desigo-pxc4-e16_manual_377108006.webp)
6
Siemens Schweiz AG
A6V11646018_en--_e
Smart Infrastructure
2021-06-11
Product documentation
Related documents such as the environmental declarations, CE declarations, etc., can be
downloaded from the following Internet address:
https://siemens.com/bt/download
Notes
Safety
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
●
Observe national provisions and comply with the appropriate safety regulations.
Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.
Ambient temperature -5...50 °C (23...122 °F)
Ambient temperature -5...45 °C (23...113 °F)
●
Wall, horizontal
– From left to right
– From right to left
●
Overhead
●
Wall, vertically
– From top to bottom
– From bottom to top
●
On a horizontal surface
CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
●
Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower out-
side the installation box.