6/12
Building Technologies
PXC...-U – Automation stations modular model
CA1N9221en
Building Automation
23.09.2005
Concerned
LED
Color
Status
Function
Automation station
RUN
Green
Red
Continuously off
Continuously on
Continuously on
No supply
Supply OK, firmware OK
RESET key pressed
STATUS
Red
Continuously
off
Continuously on
Quick flashes
Normal operation
Hardware fault detected during self-test or
automation station in "coma" operating state
No validly licensed firmware
INFO
Red
Freely
programmable
Data traffic LON bus
TX COM1 Yellow
Flashing
Data traffic on LON bus
COM2
Yellow
Inactive
SERVICE
COM1
Red Continuously
off
Flashing
Flashing acc. to wink
command pattern *)
Continuously on
LON node is configured
LON node is not configured
Physical identification of automation station
after receiving wink command
LON chip defect or service key was pressed
again
COM2
Red
Inactive
Data traffic Ethernet / IP
TX COM1 Yellow
Inactive
(PXA30-N..., PXA30-W...)
COM2 Yellow
Flashing
Sends Ethernet data
SERVICE
COM1
Red
Inactive
COM2
Red
Continuously
off
Flashing slowly
Continuously on
Ethernet OK
IP address not configured
No link pulse
*) Wink command rhythm pattern:
2s
1s
21s
5 Hz
5 Hz
00408
2s
1s
Mounting instructions
The modular automation stations are particularly suitable for control panel front
mounting as well as flush-panel and wall mounting.
For control panel front mounting the device socket is held in place by clamps at all four
corners (no tools required for mounting). The upper housing is fixed to the device
socket with two screws.
For flush panel mounting the plug-in terminal blocks can be repositioned whilst at the
same time reversing the support bars to enable front access. The support bars absorb
the screw force and also provide the means of fixing the device to the wall.
Instead of the front cover a PXM... operator unit can be fitted on the modular auto-
mation station.
For
PXM20-E
mounting (ethernet cable) see the mounting instructions delivered with
the operator unit!
•
Insert
the
PXA30… extension module
fully
into its socket (
to a depth of
1.5 mm),
using slight force.
Then
check that the plug is safely snapped on
to ensure safe
and smooth functioning.
•
Do not touch
the connector pins (electrostatic discharge)
Note
STOP
Note!
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.