10/12
Building Technologies
PXC...-U – Automation stations modular model
CA1N9221en
Building Automation
23.09.2005
Connection terminals
00341
C1
C2
C3
C4
S
S
CLA
CLB
8
9
10
G
G0
PD
PC
CP+
CP–
1
2
4
PU
MMI/TOOL
G/G0
Supply voltage AC 24 V/PELV
PD
P-bus Synchronisation
cable
PU
Data transmission line, bi-directional
PC
Reference voltage DC 23 V (against G0)
CP+/CP–
PPS2 bus (for QAX... room operator units)
CLA/CLB
LON bus
(inactive, if a PXA30-N... or PXA30-W... extension module
for Ethernet is plugged in)
HMI/TOOL
RJ45 socket on front cover
(for PXM10 / PXM20 operator unit or DESIGO TOOLSET)
The PXA-C128-U includes a second P-bus:
•
Terminals P-bus 1 PD1, PU1 and PC1
•
Terminals P-bus 2 PD2, PU2 and PC2
The automation station PXC00-U does not have an active P-Bus interface
Standard RJ45 tool socket for LON devices.
1
32
0
6
Z
0
1
2 3 4 5 6 7 8
1
LON, Data A (CLA) *)
2
LON, Data B (CLB) *)
3 G0,
GND
4 G/Plus
5 Unoccupied
6 Unoccupied
7 COM1/TxD
8 COM1/RxD
*) The LON pins are inactive, if a PXA30-N... or PXA30-W... extension module for
Ethernet is plugged in, and in the automation station PXC00-U)
Connection diagrams
Connection of field devices: see mounting and installation manual for I/O modules and
P-bus (CM2M8102).
PXC64-U
PXA-C128-U
PXC00-U
Tool socket
.
.
.
.
.
.
.
.