RS485 interface
Interface type
RS485, (electrically isolated)
Baud rate, data bits / stop bit(s), parity
As for RS232 (depends on software)
Cable type
Cable length
Standard RS bus cable
Max. 1200 m
Plug-in screw terminal
Solid or stranded conductors
0.25…2.5 mm2 or 2 x 1.5 mm2
Simple cable lengths, cable
types
Connection cable
Ethernet and
PXM20-E
Max. 100 m
Cable type
Standard at least CAT5
UTP (Unshielded Twisted Pair)
or STP (Shielded Twisted Pair)
Connection cable
L
ON
W
ORKS
bus
See Installation Guide CA110396
Cable type
CAT5
Housing protection standard Protection standard
IP 20 to IEC 60529
Protection class
Protection class
III to EN 60730
Ambient conditions
Normal operation
To IEC 60721-3-3
Environmental conditions
Class 3K5
Temperature
0...50 °C
Humidity
5…95 % r.h. (non-condensing)
Mechanical conditions
Class 3M2
Transport
To IEC 60721-3-2
Environmental conditions
Class 2K3
Temperature
-25…70 °C
Humidity
5…95 % r.h. (non-condensing)
Mechanical conditions
Class 2M2
Standards, directives and
approvals
Product standard
EN 60730-1
AMEV: Supports profiles AS-A and AS-B to
AMEV directive "BACnet in public
buildings"
Document download
www.hqs.sbt.siemens.com/gip/general/dlc/dl
c_mobile_direct.asp?BPZ:PXC001
Environmental compatibility
The product environmental declaration
CM1E9223 contains data on
environmentally compatible product design
and assessments (RoHS compliance,
materials composition, packaging,
environmental benefit, disposal)
ISO 14001 (Environment)
ISO 9001 (Quality)
Dimensions
See “Dimensions”
Weight
Without / with packaging
PXC001.D, PXC001-E.D
PXA-40-RS1, PXA40-RS2
0.635 kg / 0.731 kg
0.048 kg / 0.060 kg
8 / 10
Siemens
PXC001 System controllers
CM1N9223en_01
Building Technologies
2014-04-04