background image

The terminal blocks are removable for easy wiring. 

 

 

Communication 

RS232/RS485:   

RX (Green) :  TX (Yellow) 

KNX:   

 

RX (Green)  

TX (Yellow) 

Service (Red) 

 

The other LEDs have the following meaning: 

 

 

 

 

Service pin 

LED 

Color

 

Activity

 

Function

 

RUN 

Green  Continuously ON 

Continuously OFF 

Power OK 

No power 

FAULT 

Red 

Continuously OFF 

Continuously ON 

Rapid flashing 

OK 

Fault 

Firmware missing / corrupt 

LOW 

BATT 

Red 

Continuously OFF 

Continuously ON 

Battery OK 

Battery empty– replace! 

COMM 

Red 

Continuously ON 

Continuously OFF 

Flashing 

Connection to switch OK 

No connection to switch 

Communication  

INFO 

Red 

 

Freely programmable 

SERVICE 

(Ethernet, 

PXC001-

E.D) 

Red 

Continuously OFF 

Continuously ON 

Flashing 

Flashing per wink 

command *) 

OK 

No connection to switch 

No IP address configured 

Physical identification of system 

controller after receipt of wink 

command 

SERVICE 

(LonTalk, 

PXC001.D) 

Red 

Continuously OFF 
Continuously ON 

 
Flashing 
Flashing per wink 

command *) 

L

ON

W

ORKS

 node is configured  

Faulty L

ON

W

ORKS

 chip, or service pin 

currently depressed 
L

ON

W

ORKS

 node is not configured 

Physical identification of system 

controller after receipt of wink 

command 

 

*)  Wink command pattern: 

 

2s

1s

21s

5 Hz

5 Hz

9222z02

2s

1s

 

 

Identification of the system controller in the IP network or L

ON

W

ORKS

 network  

See "Commissioning". 

 

 

Engineering 

See the PX open documents in folder CM110761. 

 

 

 

Terminal blocks 

LED indicators 

Service pin 

4 / 10 
Siemens 

PXC001   System controllers 

CM1N9223en_01 

Building Technologies 

 

2014-04-04 

Содержание DESIGO PX Series

Страница 1: ...omation level via BACnet System controllers for the integration of Desigo RXB RXL room controllers Native BACnet devices with communication via BACnet LonTalk or BACnet IP BTL label BACnet communications passed the BTL test Comprehensive management and system functions alarm management time scheduling trends remote management access protection etc Supports operation via local or network compatible...

Страница 2: ...m Controller for the integration of KNX M Bus Modbus or SCL over BACnet LonTalk PXC001 D System Controller for the integration of KNX M Bus Modbus or SCL over BACnet IP PXC001 E D Option modules Type Up to 800 data points PXA40 RS1 SCL up to 1000 data points M Bus and Modbus up to 2000 data points PXA40 RS2 Equipment combinations PXC001 D PXC001 E D PXA40 RS1 PXA40 RS2 Interfaces KNX X Serial RS23...

Страница 3: ... screw terminal block RS485 11 RS232 interface 12 Plug in screw terminal block KNX 13 RJ45 interface ETS tool for service use 14 KNX programming pin 15 RJ45 interface for operator unit or PX KNX tool 16 Slider for mounting on DIN rail PXA40 RS RX TX SERVICE RX TX RS232 RS485 KNX SERVICE INFO COMM LOW BATT FAULT RUN HMI TOOL HMI 5 4 CLB CLA 1 2 3 6 7 8 RS485 RS232 9 10 CE SERVICE KNX TOOL CE 2b 922...

Страница 4: ...Continuously OFF Continuously ON Flashing Flashing per wink command OK No connection to switch No IP address configured Physical identification of system controller after receipt of wink command SERVICE LonTalk PXC001 D Red Continuously OFF Continuously ON Flashing Flashing per wink command LONWORKS node is configured Faulty LONWORKS chip or service pin currently depressed LONWORKS node is not con...

Страница 5: ...ique identification in the network BACnet IP or BACnet LonTalk press the Service button with a long pointed object or send a wink command to the appropriate system controller service LED blinks Variant via V24 If the Force Firmware Download Key is pressed for approx 10 s during a restart reset the current D MAP program is deleted from the FLASH The system controller waits briefly for the signal to...

Страница 6: ...as power Insert new battery correctly Note the special disposal notes on Li batteries A wrist strap and grounding cable must be used to avoid hardware damage through electrostatic discharge ESD Firmware and operating system stored in non volatile Flash ROM Flash ROM memory can be easily updated on the plant when a new firmware version is available Disposal The devices are classified as waste elect...

Страница 7: ... Level Network LonWorks FT5000 Transceiver Twisted Pair 78 kBit s Screw terminals BACnet on UDP IP IEEE802 3 Auto sensing 10 Base T 100 Base TX RJ45 shielded Local Communication HMI Tool PXM10 RS232 PXM20 BACnet LonTalk RJ45 Tool RJ45 Local Communication HMI PXM10 RS232 PXM20 BACnet LonTalk RJ45 PXM10 RS232 One PXM10 operator unit and one PXM20 per system controller may be connected But not twice ...

Страница 8: ...Mechanical conditions Class 3M2 Transport To IEC 60721 3 2 Environmental conditions Class 2K3 Temperature 25 70 C Humidity 5 95 r h non condensing Mechanical conditions Class 2M2 Standards directives and approvals Product standard EN 60730 1 CM1T9223xx CM1T9222en_C1 Zertifikat AMEV Supports profiles AS A and AS B to AMEV directive BACnet in public buildings BACnet 2011 V1 1 http database ul com Do...

Страница 9: ... 8 7 6 5 43 2 1 1 KNX data CE 2 KNX data CE 3 Not used 4 Not used 5 Not used 6 Not used 7 Not used 8 Not used 9281z04 1 2 3 4 5 6 7 8 9 1 DCD Data carrier detect 6 DSR Data set ready 2 RXD Received data 7 RTS Request to send 3 TXD Transmit data 8 CTS Clear to send 4 DTR Data terminal ready 9 NC Not connected 5 GND Signal ground Plug in screw terminal block 6 Tx 7 Rx 8 Screen connected to functiona...

Страница 10: ... 143 46 15 38 5 50 8 70 256 271 5 133 5 149 4 90 44 3 32 5 9223M01 All dimensions in mm 2014 Siemens Switzerland Ltd Subject to change 10 10 Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014 04 04 ...

Отзывы: