The terminal blocks are removable for easy wiring.
Communication
RS232/RS485:
RX (Green) : TX (Yellow)
KNX:
RX (Green)
TX (Yellow)
Service (Red)
The other LEDs have the following meaning:
Service pin
LED
Color
Activity
Function
RUN
Green Continuously ON
Continuously OFF
Power OK
No power
FAULT
Red
Continuously OFF
Continuously ON
Rapid flashing
OK
Fault
Firmware missing / corrupt
LOW
BATT
Red
Continuously OFF
Continuously ON
Battery OK
Battery empty– replace!
COMM
Red
Continuously ON
Continuously OFF
Flashing
Connection to switch OK
No connection to switch
Communication
INFO
Red
Freely programmable
SERVICE
(Ethernet,
PXC001-
E.D)
Red
Continuously OFF
Continuously ON
Flashing
Flashing per wink
command *)
OK
No connection to switch
No IP address configured
Physical identification of system
controller after receipt of wink
command
SERVICE
(LonTalk,
PXC001.D)
Red
Continuously OFF
Continuously ON
Flashing
Flashing per wink
command *)
L
ON
W
ORKS
node is configured
Faulty L
ON
W
ORKS
chip, or service pin
currently depressed
L
ON
W
ORKS
node is not configured
Physical identification of system
controller after receipt of wink
command
*) Wink command pattern:
2s
1s
21s
5 Hz
5 Hz
9222z02
2s
1s
Identification of the system controller in the IP network or L
ON
W
ORKS
network
See "Commissioning".
Engineering
See the PX open documents in folder CM110761.
Terminal blocks
LED indicators
Service pin
4 / 10