Siemens D2300CPS Скачать руководство пользователя страница 7

7

*

*

EOLR

120 OHMS, 1/4W

P/N 140-820150

RS-485 RATINGS:

8V P-P
150mA MAX
80 OHMS MAX
18 AWG MIN

1

2

3

4

EOLR

120 OHMS, 1/4W

P/N 140-820150

EOLR

120 OHMS, 1/4W

P/N 140-820150

*

OMIT THIS EQUIPMENT FOR STYLE 4 XNET

REFER TO NIM-1R OR NIM-1W
INSTALLATION INSTRUCTIONS
P/N 315-092953 OR P/N 315-099165,
AS APPLICABLE

TB3

NIM-1R/-1W

MOM-4

D2300CPS*

D2300CPS

-4

-3

-2

-1

-4

-3

-2

-1

(DO NOT USE)

(DO NOT USE)

-DATA

+DATA

(DO NOT USE)

(DO NOT USE)

-DATA

+DATA

SUPERVISED

SUPERVISED

t

n

e

r

r

u

C

e

l

u

d

o

M

C

D

V

4

2

e

v

i

t

c

A

A

m

6

6

t

n

e

r

r

u

C

e

l

u

d

o

M

C

D

V

4

2

y

b

d

n

a

t

S

A

m

6

6

Figure 8

Wiring the RS-485 XNET Network

in Style 4 and Style 7 (MXL)

RS-485 NETWORK

The RS-485 MNET, XNET and HNET networks connect
to the D2300CPS on the terminal block with the mark-
ings +DATA (1) and -DATA(2). 

Terminals 3 and 4 are

not used.

 For Style 4 networks one D2300CPS is

needed at each Fiber Optic drop. For Style 7 networks
two D2300CPS modules are needed at each drop.End
of line devices are required on each RS-485 pair in the
system. Install them at the extreme ends of each pair.
Refer to Figures 7 and 8 (MXL) Figure 9 (FireFinder
XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular) and Figure 10 (HUB-4 FSI) for wiring instruc-
tions and ratings for both Style 4 and Style 7.

NOTE:

Positive and negative ground fault detected
when terminals shorted to earth.

FIBER CONNECTIONS

The D2300CPS can function as both a

 repeater 

and an

end point

 unit. 

When used as an end point,

 connect

to the fiber connectors labeled 

A

. Make no connec-

tion to the 

B

 connectors.

 In the repeater mode,

 use

both pairs of connectors, 

A

 and 

B

.

Two Fiber Optic cables are required between each pair
of D2300CPS modules. Use a high quality duplex Fiber
Optic cable containing either 50/125 or 62.5/125 fiber.
Duplex fiber optic cable has two cables in a single
shield similar to electrical

 zip cord

. Use ST style fiber

connectors. 

Please contact the fiber manufacturer

regarding instructions for terminating the fiber.

When installing the fiber pairs, each fiber must
connect between the transmit data (DATA XTMR) on
one D2300CPS and the receive data line (DATA
REC) on the other D2300CPS.

The D2300CPS fiber connection is classified as Style
DCLB and Style DCLA per ULC-527.

INDICATORS

The D2300CPS has five LED indicators for Power
and Status.

The LEDs are located on the side of the module with
the Fiber Optic connectors. The 

Power

 LED is green

and lights whenever there is 24 VDC. Both channels 

A

and 

B

 have a yellow and green LED. The green LED

indicates that the D2300CPS is transmitting data on that
channel. The yellow LED lights when data is received.

ELECTRICAL RATINGS

Input Power

18-31 VDC, 66mA max

Battery Power

24 VDC, 66mA max

RS-485

8V (P-P), 150mA

 

max

Содержание D2300CPS

Страница 1: ...P N 500 692880 is available for mounting the D2300CPS in any MXL enclosure that will accept a MOM 4 See Figure 4 This bracket has the same footprint as the MOM 4 and accommodates two D2300CPS modules An assembly kit is included with the bracket that contains four nuts and eight screws Mount the bracket in the enclosure with the four nuts at the positions labeled X See Figure 4 Start four of the 6 ...

Страница 2: ... REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 DATA XTMR DATA XTMR POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 DATA XTMR DATA XTMR POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 SUPERVISED EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N...

Страница 3: ...DATA XTMR DATA XTM POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 PSR 1 EOLR 120 OHMS 1 4W P N 140 820150 PSR 1 RS 485 32 NODES MAX SUPERVISED NO CONNECTION NO CONNECTION NO CONNECTION SUPERVISED TO ADDITIONAL D2300CPS MODULES MULTI MODE DUPLEX OPTICAL FIBER POWER BUDGET MAX LOSS 8 dB 62 5 125 FIBER 6 dB 50 125 FIBER USE THE 120 W 5 EOL RESISTOR ASSEM...

Страница 4: ...CPS D2300CPS CAB 1 XNET FAIL XNET STYLE 7 ENABLED CAN ACTIVE NETWORKS HNET XNET STYLE GROUND FAULT NETWORK PORT LOOP B FAIL GND FAULT LOOP A FAIL STYLE 4 DISABLED HNET CARD FAIL HNET FAIL CAN FAIL RESET POWER NIC C Z 2 O N E 1 E N O Z ALARM CLASS A OPEN CLASS A RETURN CLASS A RETURN CLASS A OPEN TROUBLE ZONES STATUS SHORT SHORT CARD FAIL GND FAULT HNET FAIL RESET POWER DLC GND FAULT 24V 12A FAIL 2...

Страница 5: ...ng the RS 485 MNET Network in Style 4 and Style 7 MOM 4 D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 NET 7 REFER TO NET 7 INSTALLATION INSTRUCTIONS P N 315 091914 1 2 3 4 TB1 STYLE 7 MNET EOLR 120 OHMS 1 4W P N 140 820150 RS 485 RATINGS 8V P P 150mA MAX 80 OHMS MAX 18 AWG MIN SU...

Страница 6: ...lation E L U D O M C D V 4 2 E V I T C A E L U D O M T N E R R U C Y T I T N A U Q L A T O T 1 M C A A m 5 8 1 C S A A m 1 4 2 C S A A m 1 6 0 0 3 I M C A m 0 4 M R C A m 5 7 4 M S C x a m A 5 1 A m 4 3 t i u c r i c r e p 4 M Z C A m 0 2 7 m r a l a n i s e n o z 4 S P C 0 0 3 2 D A m 6 6 4 2 B K M A m 0 4 T E N A m 0 7 T E N A m 0 M 7 T E N A m 0 7 I O M A m 0 2 1 6 1 D O M x a m A m 0 5 8 6 1 D...

Страница 7: ...NOTE Positive and negative ground fault detected when terminals shorted to earth FIBER CONNECTIONS The D2300CPS can function as both a repeater and an end point unit When used as an end point connect to the fiber connectors labeled A Make no connec tion to the B connectors In the repeater mode use both pairs of connectors A and B Two Fiber Optic cables are required between each pair of D2300CPS mo...

Страница 8: ... P 150mA MAX 80 OHMS MAX 18 AWG MIN NO EOLR REQUIRED AT THE NIC C STYLE 4 HNET XNET STYLE 7 HNET XNET 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DO NOT USE DO NOT USE DO NOT USE DO NOT USE ONE SLOT OF CC 5 CC 2 NIC C SUPERVISED SUPERVISED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DO NOT USE DO NOT USE DO NOT USE ONE SLOT OF CC 5 CC 2 NIC C D2300CPS 4 3 2 1 ...

Страница 9: ...18 19 20 21 22 23 24 ONE SLOT OF CC 5 CC 2 HUB 4 SUPERVISED SUPERVISED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 A PORT 2 ONE SLOT OF CC 5 CC 2 HUB 4 D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA EOLR 120 OHMS 1 4W P N 140 820150 SUPERVISED D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA PORT 1 B B A A B B A A B B A A B B A A B B A A B B A RS 485 INTERFACE Port 3 RS 485 IN...

Страница 10: ...security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional information on...