Siemens D2300CPS Скачать руководство пользователя страница 5

5

Figure 6

Wiring the D2300CPS as both a Repeater and End Point Unit

D2300CPS

D2300CPS

D2300CPS

SUPERVISED

POWER BUDGET - MAX LOSS

-8 dB 62.5/125 FIBER
- 6 dB

50/125 FIBER

N.C.

N.C.

END POINT

RS-485 NETWORK
MNET/HNET/XNET
(SEE FIGURES 7, 8 & 9)

FACP

FACP

FACP

REPEATER

SUPERVISED

POWER BUDGET - MAX LOSS

-8 dB 62.5/125 FIBER
- 6 dB

50/125 FIBER

END POINT

N.C.

N.C.

DATA

REC

DATA

XTMR

DATA

REC

DATA

XTMR

A

B

DATA

REC

DATA

XTMR

DATA

REC

DATA

XTMR

A

B

DATA

REC

DATA

XTMR

DATA

REC

DATA

XTMR

A

B

Figure 7

Wiring the RS-485 MNET Network in Style 4 and Style 7

MOM-4

D2300CPS

-4
-3
-2
-1

(DO NOT USE)
(DO NOT USE)

-DATA

+DATA

D2300CPS

-4
-3
-2
-1

(DO NOT USE)
(DO NOT USE)

-DATA

+DATA

EOLR

120 OHMS, 1/4W

P/N 140-820150

EOLR
120 OHMS, 1/4W
P/N 140-820150

NET-7

REFER TO NET-7
INSTALLATION INSTRUCTIONS
P/N 315-091914

1

2

3

4

TB1

STYLE 7 MNET

EOLR

120 OHMS, 1/4W

P/N 140-820150

RS-485 RATINGS:

8V P-P
150mA MAX
80 OHMS MAX
18 AWG MIN

SUPERVISED

SUPERVISED

MMB

D2300CPS

-4
-3
-2
-1

(DO NOT USE)
(DO NOT USE)

-DATA

+DATA

TB1

(DO NOT USE)

(DO NOT USE)

4

3

2

1

STYLE 4 MNET

RS-485 RATINGS:

8V P-P
150mA MAX
80 OHMS MAX
18 AWG MIN

SUPERVISED

USE THE 120

¼ W, 5%

EOL RESISTOR ASSEMBLY,
AS APPLICABLE:
P/N 140-820150 (MMB-1/-2)
OR P/N 140-049099 (MMB-3)

W,

Содержание D2300CPS

Страница 1: ...P N 500 692880 is available for mounting the D2300CPS in any MXL enclosure that will accept a MOM 4 See Figure 4 This bracket has the same footprint as the MOM 4 and accommodates two D2300CPS modules An assembly kit is included with the bracket that contains four nuts and eight screws Mount the bracket in the enclosure with the four nuts at the positions labeled X See Figure 4 Start four of the 6 ...

Страница 2: ... REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 DATA XTMR DATA XTMR POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 DATA XTMR DATA XTMR POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 SUPERVISED EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N...

Страница 3: ...DATA XTMR DATA XTM POWER B A DATA REC DATA REC D2300CPS POWER 24 VDC 1 2 DO NOT USE 4 DO NOT USE 3 DATA 2 DATA 1 PSR 1 EOLR 120 OHMS 1 4W P N 140 820150 PSR 1 RS 485 32 NODES MAX SUPERVISED NO CONNECTION NO CONNECTION NO CONNECTION SUPERVISED TO ADDITIONAL D2300CPS MODULES MULTI MODE DUPLEX OPTICAL FIBER POWER BUDGET MAX LOSS 8 dB 62 5 125 FIBER 6 dB 50 125 FIBER USE THE 120 W 5 EOL RESISTOR ASSEM...

Страница 4: ...CPS D2300CPS CAB 1 XNET FAIL XNET STYLE 7 ENABLED CAN ACTIVE NETWORKS HNET XNET STYLE GROUND FAULT NETWORK PORT LOOP B FAIL GND FAULT LOOP A FAIL STYLE 4 DISABLED HNET CARD FAIL HNET FAIL CAN FAIL RESET POWER NIC C Z 2 O N E 1 E N O Z ALARM CLASS A OPEN CLASS A RETURN CLASS A RETURN CLASS A OPEN TROUBLE ZONES STATUS SHORT SHORT CARD FAIL GND FAULT HNET FAIL RESET POWER DLC GND FAULT 24V 12A FAIL 2...

Страница 5: ...ng the RS 485 MNET Network in Style 4 and Style 7 MOM 4 D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA EOLR 120 OHMS 1 4W P N 140 820150 EOLR 120 OHMS 1 4W P N 140 820150 NET 7 REFER TO NET 7 INSTALLATION INSTRUCTIONS P N 315 091914 1 2 3 4 TB1 STYLE 7 MNET EOLR 120 OHMS 1 4W P N 140 820150 RS 485 RATINGS 8V P P 150mA MAX 80 OHMS MAX 18 AWG MIN SU...

Страница 6: ...lation E L U D O M C D V 4 2 E V I T C A E L U D O M T N E R R U C Y T I T N A U Q L A T O T 1 M C A A m 5 8 1 C S A A m 1 4 2 C S A A m 1 6 0 0 3 I M C A m 0 4 M R C A m 5 7 4 M S C x a m A 5 1 A m 4 3 t i u c r i c r e p 4 M Z C A m 0 2 7 m r a l a n i s e n o z 4 S P C 0 0 3 2 D A m 6 6 4 2 B K M A m 0 4 T E N A m 0 7 T E N A m 0 M 7 T E N A m 0 7 I O M A m 0 2 1 6 1 D O M x a m A m 0 5 8 6 1 D...

Страница 7: ...NOTE Positive and negative ground fault detected when terminals shorted to earth FIBER CONNECTIONS The D2300CPS can function as both a repeater and an end point unit When used as an end point connect to the fiber connectors labeled A Make no connec tion to the B connectors In the repeater mode use both pairs of connectors A and B Two Fiber Optic cables are required between each pair of D2300CPS mo...

Страница 8: ... P 150mA MAX 80 OHMS MAX 18 AWG MIN NO EOLR REQUIRED AT THE NIC C STYLE 4 HNET XNET STYLE 7 HNET XNET 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DO NOT USE DO NOT USE DO NOT USE DO NOT USE ONE SLOT OF CC 5 CC 2 NIC C SUPERVISED SUPERVISED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DO NOT USE DO NOT USE DO NOT USE ONE SLOT OF CC 5 CC 2 NIC C D2300CPS 4 3 2 1 ...

Страница 9: ...18 19 20 21 22 23 24 ONE SLOT OF CC 5 CC 2 HUB 4 SUPERVISED SUPERVISED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 A PORT 2 ONE SLOT OF CC 5 CC 2 HUB 4 D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA EOLR 120 OHMS 1 4W P N 140 820150 SUPERVISED D2300CPS 4 3 2 1 DO NOT USE DO NOT USE DATA DATA PORT 1 B B A A B B A A B B A A B B A A B B A A B B A RS 485 INTERFACE Port 3 RS 485 IN...

Страница 10: ...security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional information on...

Отзывы: