Installation and Circuitry
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
189
DC8-037-2.02, Edition 10.2017
6.5.2
Mounting of the Master Module
CP-802x can be installed on the DIN rail by hand, without any tools.
The Master Module is equipped
with a bus connector. Remove the
bus connector from the module
and click it on the DIN rail.
Press the module on the bus
connector. This opens the locking
hooks.
When module and bus connector
are connected correctly, the lock-
ing hooks are latched on the DIN
rail.
Note
You also can open and lock the locking hooks on the module, before you mount the module. They must be
closed manually after assembly.
3
2
1