background image

3

ALARM SILENCE

The internal momentary 

ALARM SILENCE 

switch is

operated to silence an existing energized audible alarm

circuit. The general alarm audible circuit may be op-

tionally silenced by momentary operation of the 

ALARM

SILENCE 

switch at any time after it has become en-

ergized. The  predischarge/discharge  audible  alarm

circuit may be optionally silenced by momentary op-

eration of the same 

ALARM SILENCE 

switch, but only

after the selected predischarge period has timed out.
Silencing the general alarm circuit prior to operation

of the predischarge audible circuit does not inhibit the

predischarge circuit audible from its normal operation.

To silence the discharge audible circuit in this case

requires a second 

ALARM SILENCE 

switch activa-

tion. After silencing either the general alarm circuit and/

or the discharge audible circuit, both remain silenced

until the panel is reset (if alarm condition cleared).

“Silence”  operation  of  either  alarm  circuit  does  not

change the state of the general alarm relay contacts.

Operation of the 

ALARM SILENCE 

switch, when the

panel is not in an alarm state, has no effect.

SUPERVISORY SILENCE

Operation of the 

SUPERVISORY SILENCE 

switch to

its Silence position results in silencing the internal su-

pervisory buzzer when the panel is in a supervisory

condition, as indicated by the supervisory light on the

front  panel.  Operation  of  the 

SUPERVISORY  SI-

LENCE 

switch to its Silence position when a panel

supervisory condition does not exist causes the su-

pervisory buzzer to operate as it does when the 

SU-

PERVISORY SILENCE 

switch is in Silence position

and the panel supervisory condition is cleared to a

normal supervisory condition.

TROUBLE SILENCE

Operation of the 

TROUBLE SILENCE 

switch to its

Silence position results in silencing the internal trouble

buzzer when the panel is in a trouble condition, as

indicated by the trouble light on the front panel. Op-

eration of the 

TROUBLE SILENCE 

switch to its Si-

lence position when a panel trouble condition does

not exist causes the trouble buzzer to operate as it

does when the 

TROUBLE SILENCE 

switch is in Si-

lence  position  and  the  panel  trouble  condition  is

cleared to a normal supervisory condition.

RELEASE DISCONNECT

The 

RELEASE DISCONNECT 

switch is a normally

closed single pole switch in series with the release

circuit output. Moving the switch from its normally closed

position during a non-discharge or circuit activation

condition causes an open circuit trouble indication of

the release circuit. This prevents the associated dis-

charge devices from activating.

If the 

ALARM SILENCE 

switch has been operated after

initiation of the first zone alarm, a second zone alarm re-

sults in reactivating the general alarm audible circuit, which

may then be silenced again.

  For NFPA 12A, 13, or 2001 Service:

• Place 

SERVICE SELECTION 

plug in P12.

• Connect TB2, terminals 5 and 6 as shown in the Con-

nection  Diagram. An  open  circuit  will  cause  a  trouble

condition.

Initiating Circuit and Agent Release Operation 

(Selec-

tion Plug Placed on P12). The two initiating zones pro-

vided are arranged so that both zones (cross zoning) must

be alarmed before the agent release discharge sequence

begins.
A single zone alarm condition results in:

1. Alarm lock-in of that zone.

2. Visual alarm indication of that zone.

3. General alarm condition of panel which includes:

a. Change of state of fire alarm relay contacts.

b. General alarm audible circuit activated.

Upon initiation of both zones, the agent discharge delay

sequence  begins. The  discharge  delay  period  may  be

preselected  by  rotating  the  Discharge  Delay  Selection

switch S101 to one of the following time-in periods: 0, 5,

10, 15, 20, 25, 30, 35, 40, or 45 second delay. (Refer to

Option No. 1 below.)
As the discharge delay period begins (both zones alarmed),

and the general alarm audible circuit is de-energized, the

predischarge  relay  contacts  (TB3,  terminals  10  through

14) change state (See Option No. 4). The predischarge au-

dible  circuit,  along  with  its  associated  visual  indicator,  is

cycled  at  a  2  Hz  rate  with  a  50%  duty  cycle  during  the

selected discharge delay period. At the conclusion of the

discharge delay period, the agent release circuit is ener-

gized for approximately 1 minute, while the discharge au-

dible is energized in a steady-on condition until either it is

silenced or the panel is reset to a non-alarm condition.

MANUAL SWITCHES

System 

RESET/LAMP TEST

Upon initiation of either Zone 1 or Zone 2 and/or op-

eration  of  the  manual 

DISCHARGE  PRESSURE

switch, the Control Panel locks into an alarm condi-

tion. This alarm condition may only be reset by opera-

tion of the internal momentary 

RESET/LAMP TEST

switch. While this switch is held in the Reset position,

all indicating lamps, except 

POWER 

and charge cur-

rent operation 

BATTERY CHARGER 

are lit. It should

be noted that the Control Panel cannot be reset while

the manual 

DISCHARGE PRESSURE 

switch is in the

closed position.

Technical Manuals Online! - http://www.tech-man.com

Содержание CP-2ER

Страница 1: ...g Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Fire Safety Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 SUPERVISORY TROUBLE ALARM ZONE 1 DISCHARGE ALARM SILENCED ALARM ZONE 2 POWER ON BATTERY WHEN FLASHING Technical Manuals Online http www tech man com ...

Страница 2: ... Contents INTRODUCTION 1 OPERATION 2 CONNECTION DIAGRAM 4 5 INSTALLATION AND WIRING 7 POWER LIMITED WIRING 8 MAINTENANCE AND TESTING 9 TROUBLESHOOTING THE SYSTEM 9 Technical Manuals Online http www tech man com ...

Страница 3: ...t ing zone causes the general alarm to sound again To set the CP 2ER to meet NFPA 12A 13 or 2001 require ments for a releasing panel place the SERVICE SELEC TION plug in position P12 Release With the plug in this position both a general alarm associated with the first ini tiating zone actuation and a predischarge discharge alarm with actuation of the second initiating zone will sound The position ...

Страница 4: ...econd zone results in only a visual display indicating that the second zone has alarmed VISUAL INDICATORS COLOR Visual Indicators Externally Visible POWER Steady on indicates main power is normal Green Flashing on off indicates panel is operating from the backup battery supply System TROUBLE Indicates a general system trouble Yellow System SUPERVISORY Indicates a general system supervisory Yellow ...

Страница 5: ...d position during a non discharge or circuit activation condition causes an open circuit trouble indication of the release circuit This prevents the associated dis charge devices from activating If the ALARM SILENCE switch has been operated after initiation of the first zone alarm a second zone alarm re sults in reactivating the general alarm audible circuit which may then be silenced again For NF...

Страница 6: ...STATION MODEL AW 1 N O CYLINDER SUPERVISORY SWITCH P N 500 878709 MANUAL DISCHARGE PRESSURE SWITCH P N 500 486536 5 6K 1 2W EOL W 2 2K 1 2W EOL W 3 2 1 POWER SUPPLY P1 INPUT 120V 50 60 HZ 2A MAX NEUTRAL P2 BATTERIES 24 VDC Charging Current Normal 300mA 24 VDC Charging Current Max 560mA Load Current Max 3 3A 4 0A with self interrupting solenoid P N 500 890181 24 HR P N 175 084476 5 AH 60 HR P N 175...

Страница 7: ... Service 7 Refer to OPERATING INSTRUCTIONS P N 315 193524 8 To use power limited wiring to NFPA 70 NEC the audible circuits terminals 1 4 of TB2 must use the PLM 35 module Refer to In structions P N 315 093495 Initiating circuits TB1 terminals 1 14 are power limited as they are 9 For a list of COMPATIBLE NOTIFICATION APPLIANCES refer to P N 315 096363 DESIGNATION RATING CIRCUIT F1 F2 F3 F4 5A 2A 2...

Страница 8: ...he delay period when the agent is re leased the discharge audibles sound in a steady manner b If the ABORT switch is depressed before the 30 second time in period ends 1 The discharge audibles are silenced during the 90 second abort duration period NOTE The 90 second delay period associated with the external abort switch is provided by others 5 Switch S101 Dial setting Rotate to change setting Dia...

Страница 9: ...eration without first consulting one of the above Mounting Control Units Refer to Figure 2 Securely fasten the control unit to a shock and vibration free surface in a clean dry area It must be mounted far ther than 3 feet but less than 6 feet from the floor The location should be easily visible readily accessible for main tenance and should allow sufficient clearance to open the hinged front door ...

Страница 10: ...ice is requested 15 days prior to the tests so that the services of the technician may be scheduled The installation of the wiring should be checked as follows 1 Detectors should not be in their bases Temporary jump ers should be inserted in all bases if not already in stalled Install end of line resistor to appropriate termi nals of last detector on circuit for Class B wiring For Class A wiring i...

Страница 11: ...2 PLM 35 If the PLM 35 module is required mount it on the left side wall of the enclosure as shown in Figure 3 Refer to PLM 35 Installation Instructions P N 315 093495 MAINTENANCE AND TESTING To insure proper and reliable operation refer to NFPA 72 Local 12A or 2001 as appropriate for applicable main tenance and testing schedule and instructions CAUTION Make sure that release circuits and shunt tr...

Страница 12: ... wiring Zone 1 and or Zone 2 initiating circuits TB1 between terminals 2 and 3 or between terminals 6 and 7 open circuited or not terminated with a 1 78K ohm resistor Wiring resistance between terminals 1 and 2 3 and 4 5 and 6 or 7 and 8 exceeds acceptable limits Refer to CONNECTION DIAGRAM on pages 4 5 7 General alarm audible alarm circuit TB2 terminals 1 and 2 open circuited or not termi nated w...

Отзывы: