Siemens CLM Series Скачать руководство пользователя страница 7

Coil Replacement 

(cont.) 

Magnet Suspension 

- refer to Figure 1 

Kickout Springs 

- refer to Figure 1 

Contactor Rating 

Main Contact Kit 

and Pole Combination 

Part Number 

300 Amp 2-Pole 

CLMGCK02 

300 Amp 3-Pole 

CLMGCK03 

400 Amp 2-Pole 

CLMHCK02 

400 Amp 3-Pole 

CLMHCK03 

Item 

Cat./Part Number 

Coil-Clearing Auxiliary Contact 

CLMHCCK11 

Auxiliary Contact 1 NO 1 NC 

CLMFCAK11 

Auxiliary Contact 2 NO 0 NC 

CLMFCAK20 

Auxiliary Contact 0 NO 2 NC 

CLMFCAK02 

• 

Voltage 

300 

600 

10,000 

400 

300 
400 

600 

10,000

Table 5 Renewal Parts

contacts (18). (A 1/4 inch Allen wrench is required for 

the  5/16 inch  socket  head  cap  screws.)  To  install  the 

new  contacts  reverse  the  procedure,  using  the  torque 

table,  Table  2.  Raise  the  crossbar  into  its  proper 

position with the moving contacts inside the arc chute. 

Install the arc chute, making sure the arc chute bolts are 

tight. Check to be sure both the kickout (6) and contact 

springs (17) are properly seated and the nameplate is in 

place. The moving contacts should touch the stationary 

contacts at the same instant within 1 /16 inch maximum 

error  on  all  poles  as  the  contactor  is  closed.  Contact 

face  misalignment  of  approximately  1/16  inch  (mea-

sure  with  the  contactor  fully  closed)  will  not  be  detri-

mental to the operation of the contactor.

Fig. 9   Spring Length Measurement 

Fig. 10   Spring Length Measurement 

Both the stationary magnet and moving magnet assem-

blies are flexibly mounted to ensure proper sealing of 

the  magnet.  Both  helical  compression  and  flat  leaf 

springs are in back of each magnet part The moving 

armature has less spring force and restraint than the 

stiffer stationary magnet assembly. In case these mag-

nets  are  ever  disassembled,  particular  care  must  be 

used  to  make  sure  that  the  flat  leaf  springs  are 

centered on the laminated magnet assemblies and are 

not  jammed  between  the  magnets  and  the  molded 

guide projections. After reassembly, be sure to check 

that  both the stationary and moving magnets can be 

manually depressed or rocked in their mountings. 

Normally  no  maintenance  is  required  for  the  kickout 

springs (6) other than to make sure they are properly 

seated  on  the  molded  crossbar  assembly.  In  case 

they are inadvertantly removed from the molded base 

where  they  are  captivated  in  a  hole  slightly  smaller 

than the free spring diameter, they can be reinstalled 

with  a  needle-nosed  plier.  Hold  the  front  end  of  the 

spring, insert the pliers inside the spring and rotate the 

offset pin end of the spring in a direction to decrease 

its outside diameter. Keep the spring restrained until 

the pin end has been inserted into the molded base. 

Thin Paper Feeler Folded 

Under Moving Contact

Mounting 

Surface

Stationary

Contact

Moving

Contact

Initial 

Length

Scale

Thin Paper 

Feeler

"Power Off”Armature 

Fully Held 

Closed Manually 

Contact Spring

Stationary

Contact

Thin Paper

Feeler

Contact 

Overtravel 

Initial

Spring Length

Final

Spring Length

=

-

Final 

Length

Moving

Contact

Table 6 - Circuit Ratings 

Contactor 

Amp. 

Rating 

Short-Circuit 

Protective Device 

(SCPD) 

Short-Circuit Current

RMS Symmetrical

Amperes

Max. Amp. 

Rating of 

SCPD 

Circuit breaker 

Circuit breaker 

7

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092

A5E49381767A

Содержание CLM Series

Страница 1: ...r closes the latch lever hooks over the latch pin to mechanically latch the contactor closed The Coil Clearing Auxiliary Contact deenergizes the closing coil Opening When the Trip pushbutton is operated the trip solenoid coil is energized unhooking the latch lever from the latch pin which allows the contactor to open As the contactor opens the Coil Clearing Auxiliary Contact deen ergizes the trip ...

Страница 2: ...Fig 1 400 Ampere CLM0H03 Contactor Exploded View 1 8 2 9 4 7 6 14 12 18 15 13 14 11 3 5 17 16 19 2 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E49381767A ...

Страница 3: ...olted in place The arc chute 2 provides the mechanical stop for the moving contact assembly while maintaining the proper open gap for the main contacts The arc chute also contains the De ion type arc quenchers Two front accessible bolts 1 hold the arc chute in place This arc chute requires no maintenance except for periodic inspection for grid damage or ceramic liner burn through by fault conditio...

Страница 4: ...nt 1 Latch Adjustment refer to Figures 1 7 and Table 2 Manually close the contactor to the fully closed position Loosen latch bolts 10 Move latch 11 to obtain 0 003 to 0 007 inch clearance shown Retighten latch bolts to 90 100 lb in while maintain ing clearance 2 Trip Solenoid Adjustment refer to Figures 1 7 and Table 2 Manually close the contactor to the fully closed position Note that the latch ...

Страница 5: ...he bolts per Table 2 Contact Overtravel and Replacement refer to Figures 1 9 10 and Tables 2 and 5 CAUTION The contactor must never be operated in power circuit unless the arc chute is securely bolted in place Remove all power from the contactor and the operating coils With new contacts the initial contact overtravel is 5 32 to 13 64 inches The overtravel is measured as shown in Figures 9 and 10 R...

Страница 6: ...of Latch and Trip Solenoid Contactor Closed Fig 8 Adjustment of Coil Clearing Auxiliary Contact Contactor Open Fig 6 CLM0H03 Dimension Drawing 6 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E49381767A ...

Страница 7: ... are in back of each magnet part The moving armature has less spring force and restraint than the stiffer stationary magnet assembly In case these mag nets are ever disassembled particular care must be used to make sure that the flat leaf springs are centered on the laminated magnet assemblies and are not jammed between the magnets and the molded guide projections After reassembly be sure to check...

Страница 8: ...matter into enclosure Remove fault and check to be sure fuse or breaker size is correct Clean and tighten Replace with new coil Handle and store new coils carefully Check coil rating and replace with correct coil Check coil marking and wiring With power off check for movement of armature contacts and latch mechanism Replace Clean pole faces with LPS CFC Free Electro Contact Cleaner Check coil coil...

Отзывы: