Description
Table 1 - Contactor Ratings
Contactor Rating
300
400
Tungsten
Max. Volts, line-line
480
480
Max. Volts, line-Neutral
277
277
Ballast
Max. Volts, line-line
600
600
Max. Volts, line-Neutral
346
346
General and Resistive
Max. Volts, line-line
600
600
Max. Volts, line-Neutral
346
346
Contactor
300A
400A
Poles
2-3
2-3
Inrush VA
1600
1600
Dropout VA
550
550
Voltage
Continuous
Make
Break
C
A
V
0
0
6
-
0
2
1
10A
7200VA
720VA
72-120 VAC
10A
60VA
720VA
28-72 VAC
10A
60VA
10VA
28-300 VDC
1A
28VA
28VA
Operation
Each contactor and its associated load should be protected
against circuits by a suitable branch circuit protective device
selected in accordance with the National Electric Code
(NEC).
E87010-A0526-T003-A6-CLM
0
Lighting Contactor
300 and 400 Amp, 2 and 3 Pole
Mechanically Latched
Model L
Catalog Number
AC Coil Data
Auxilliary Contact Ratings (A600, R300)
Closing
- When the "Close" pushbutton is operated, the
closing coil is energized, closing the contactor. As the
contactor closes, the latch lever hooks over the latch pin to
mechanically latch the contactor closed. The Coil Clearing
Auxiliary Contact deenergizes the closing coil.
Opening
- When the ''Trip" pushbutton is operated, the trip
solenoid coil is energized, unhooking the latch lever from
the latch pin, which allows the contactor to open. As the
contactor opens, the Coil-Clearing Auxiliary Contact deen-
ergizes the trip solenoid coil.
Care should be taken when servicing that the leads do not
become changed from their terminals, or improper opera-
tion and possibly permanent damage to the contactor
could result.
CAUTION:
Avoid attempting to manually latch or delatch
the contactor.
CLM0G... CLM0H...
Coil Data - Typical Values
1
Instructions
Installation
Maintenance
Parts List
July, 2019
WARNING
Hazardous voltage can cause electrical shock and
burns. May cause death, serious injury or
property damage.
Mechanically Latched CLM contactors are UL Listed
and CSA Certified for tungsten, ballast general and
resistive loads. (Table 1 below shows the voltage and
current ratings for the various loads.)
Continuous Current Rating, Amp.
Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092
A5E49381767A