PXL Conventional Fire Alarm Control Panel
Installation
14
STEP 5Install the Optional PNC-2Z
CAUTION
The PPS-10M Power Supply module must be installed before
mounting and wiring the PNC-2Z
notification module.
Setting the Address
Before mounting the PNC-2Z to the PMK-1 bracket, set the address on
Switch S1 according to Table 3. (Refer to Figure 9 for the location of S1 and
to the Note on page 9 for the operation of the switches.)
X = SWITCH CLOSED OR ON, O = SWITCH OPEN OR OFF
Figure 9
PNC-2Z Module Board
TABLE 3
SETTING THE ADDRESS ON THE
PNC-2Z
Module
Number
NAC
Range
Switch Setting
1 2 3 4 5
1
9-10
X
O
O
O
O
2
11-12
O
X
O
O
O
3
13-14
X
X
O
O
O
4
15-16
O
O
X
O
O