B3R051 Parallel indicator terminal (supersedes B3R050)
197
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
47
B3R051 Parallel indicator terminal
(supersedes B3R050)
47.1 Overview
B3R051 AlgoPilot
B3Q…
Î
Templates for inscription strips see document 006516
z
Option to control terminal AlgoPilot B3Q... or to LON/Mimic Display converter
K3I050
z
Allows additional display fields
z
Unit with 2 x 12 display fields each with a red and yellow LED
z
Individual allocation of individual display fields
z
Max. 24 units, however max. 8 addresses
z
Communication is via a special serial bus
z
Line and device
not
monitored
z
”Lamp test” is contained in the menu function of AlgoPilot B3Q...
47.2 Application
Installation
The parallel indicator terminal B3R051 fits in the following housings:
–
plastic housing ”small” H23G220 (1x B3R051)
–
housing H28G200 with door H28T120 for 4x B3R051
with door H28T130 for 1x B3R051 (and plan compartment)
Positioning
Immediately next to or in the immediate vicinity of the control terminals AlgoPilot
B3Q... or up to 1000m away in a separate housing
47.3 Key
data
Operating voltage
9..45 VDC
Current consumption
at 24 V
at 9 V
at 45 V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA