instabus EIB

 

Technical Product Information 

September 2001 

Binary Input N 260  

5WG1 260-1AB01 

 

4 x 230 V AC 

Location and Function of the Display and  
Operator Elements  

 

A1

A2

A4

A3

A5

 

 

Figure 1: Location of the display and operator elements 

 
A1  LED for indicating normal operating mode (LED off) 

and addressing mode (LED on); upon receiving the 
physical address the device automatically returns to 
normal operating mode 

A2  Learning button  for switching  between normal 

operating mode and addressing mode for receiving 
the physical address 

A3 Type 

plate 

A4  Screwless plug-in terminals for connecting input 

circuits 

A5  Label for noting the physical address 
 
 

Mounting and Wiring 

 
General description 
The N-system DIN-rail device (2 SUs) can be installed to 
N-system distribution boards, surface or flush mounted, 
or to any DIN-rail EN 50022-35 x 7,5 available that has a 
data rail installed. 
The connection to the bus line is established by clicking 
the device onto the DIN-rail (with a data rail installed). 
Take care that the type plates of all devices on a DIN-rail 
can be read in the same direction, guaranteeing the 
devices are polarised correctly. 
 

Mounting DIN-rail devices (Figure 2) 

Slide the device (B1) onto the DIN-rail (B2) and 

swivel back the device until the slide clicks into place 
audibly. 

 
Dismounting DIN-rail devices (Figure 2) 

Remove all connected wires, 

press down the slide (C3) with a screw-driver and 

swivel the device (C1) from the DIN-rail (C2). 

 

B1

C1

C2

C3

B2

 

 

Figure 2: Mounting and dismounting a DIN-rail device 

 
Connecting input circuits (Figure 3) 

The load circuits are connected via screwless plug-in 
terminals (D1). 

Remove approx. 9 to 10 mm of insulation from the 
wire (D1.1) and plug it into the terminal (D1). 

 
Conductor cross sections: 

• 

signal inputs, physical: 
strip insulation for 9 ... 10 mm 
permissible conductor types/cross sections: 

0,5 ... 2,5 mm² single core or flexible conductor,  
8 mm ultrasonically compacted 

0,5 ... 2,5 mm² flexible conductor with terminal pin, 
crimped on gas tight 

0,5 ... 1,5 mm² flexible conductor with connector 
sleeve 

1,0 and 1,5 mm² plain flexible conductor 

 
Disconnect input circuits (Figure 3) 

Press the terminal lock (E1.2) with a screw-driver and 

remove the wire (E1.1) from the terminal (E1). 

 

 

E1.2

E1

E1.1

D1

D1.1

9 ... 10 mm

 

 

Figure 3: Connecting and disconnecting wires 

Siemens AG 

N 260, 4 pages 

Technical Manual 

Automation and Drives Group 

 

 

Electrical Installation Technology 

 Siemens AG 2001 

Update: http://www.siemens.de/installationstechnik 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.7.1.3/3 

Содержание Binary Input N 260

Страница 1: ...or dimmer shutter or on off sending value switching at leading edge or at leading and trailing edge switching short long key depression sending value at leading edge or at leading and trailing edge duration of long key depression can be set used type of contacts can be set 11 S4 BinVal 240A01 4 binary inputs each input allows to send values at leading edge and or at leading and trailing edge allow...

Страница 2: ...mm flexible conductor with terminal pin crimped on gas tight 0 5 1 5 mm flexible conductor with connector sleeve 1 0 and 1 5 mm plain flexible conductor V WARNING When looping through the shared N conductor connection blocks 3 and 6 take care that the maximum connection current of 2 A as governed by the maximum permissible printed conductor load is not exceeded bus line pressure contacts on data r...

Страница 3: ...es Figure 2 Slide the device B1 onto the DIN rail B2 and swivel back the device until the slide clicks into place audibly Dismounting DIN rail devices Figure 2 Remove all connected wires press down the slide C3 with a screw driver and swivel the device C1 from the DIN rail C2 B1 C1 C2 C3 B2 Figure 2 Mounting and dismounting a DIN rail device Connecting input circuits Figure 3 The load circuits are...

Страница 4: ...am Dimensions in mm b 90 44 55 45 b 2 SU 1 Spacer unit SU 18mm Notes Technical Manual N 260 4 pages Siemens AG Automation and Drives Group Update http www siemens de installationstechnik Siemens AG 2001 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 7 1 3 4 ...

Отзывы: