Siemens Binary Input N 260 Скачать руководство пользователя страница 2

instabus EIB

 

Technical Product Information 

September 2001 

Binary Input N 260  

5WG1 260-1AB01 

 

4 x 230 V AC 

Technical Specifications 

 

Power supply 

Technical Manual 

N 260, 4 pages 

Siemens AG 

via bus cable 
 

Inputs 

• 

4 inputs 

• 

input signal voltage : 

rated value: AC 230 V  

frequency: 47 ... 63 Hz 

signal ''0'': 0 ... 170 V 

signal ''1'': 198 ... 264 V 

• 

input (signal) current at ''1'':usually 1 mA (at AC 230 V) 

• 

delay of input signal: 

at leading edge of input signal: max. 5 ms 

at trailing edge of input signal: max. 30 ms 

• 

duration of input signal: min. 50 ms 

• 

input characteristic: set in parameter list according to 
application program 

• 

length of input signal cable: max. 100 m unshielded 

• 

glow lamps for illuminating push buttons: 
maximum number of glow lamps that can be 
connected via a bridging module 5TC5 015 to each 
input: 

high luminous power (5TG7 342):       max. 12 units 

medium luminous power (5TG7 332): max. 18 units 

low luminous power (5TG7 321):         max. 60 units 

 

Control elements 

1 learning button: 
for switching between normal operating mode and 
addressing mode 
 

Display elements 

1 red LED: 
for monitoring bus voltage and displaying mode, 
selected with the learning button. 
 

Connections 

• 

signal inputs, physical: 
strip insulation for 9 ... 10 mm 
permissible conductor types/cross sections: 

0,5 ... 2,5 mm² single core or flexible conductor,  
8 mm ultrasonically compacted 

0,5 ... 2,5 mm² flexible conductor with terminal pin, 
crimped on gas tight 

0,5 ... 1,5 mm² flexible conductor with connector 
sleeve 

1,0 and 1,5 mm² plain flexible conductor 

 

V

 WARNING

 

 

When  looping through  the shared  N-conductor 
(connection blocks 3 and 6), take care that the maximum 
connection current of 2 A (as governed by the maximum 
permissible printed conductor load) is not exceeded! 
 

• 

bus line, pressure contacts on data rail 

 

Physical specifications 

• 

housing: plastic 

• 

N-system DIN-rail mounted device, 
width: 2 SUs (1SU = 18mm) 

• 

weight: approx. 150 g 

• 

fire load: approx. 2250 kJ 

±

 10 % 

• 

installation: rapid mounting on 
DIN EN 50022-35 x 7,5 rail 

 

Electrical safety 

• 

fouling class (according to IEC 664-1): 2 

• 

protection (according to EN 60529): IP 20 

• 

overvoltage class (according to IEC 664-1): III 

• 

bus: safety extra low voltage SELV DC 24 V 

• 

the device complies with 
EN 50090-2-2 and EN 60669-2-1  

 

Reliability

 

rate of failure: 612 fit at 40 

°

 

Electromagnetic compatibility

 

complies with 
EN 50081-1, EN 50082-2 and EN 50090-2-2 
 

Environmental specifications

 

• 

climatic conditions: EN 50090-2-2 

• 

ambient temperature operating: - 5 ... + 45 

°

• 

ambient temperature non-op.: - 25 ... + 70 

°

 C 

• 

relative humidity (non-condensing): 5 % to 93 % 

 

Certification

 

EIB certificate 
 

CE norm

 

complies with the EMC regulations (residential and 
functional buildings), and low voltage regulations 
 

 

 

Automation and Drives Group 

Update: http://www.siemens.de/installationstechnik 

 Siemens AG 2001 

Electrical Installation Technology 

 

Subject to change without prior notice 

P.O.Box 10 09 53, D-93009 Regensburg 

2.7.1.3/2

 

 

 

Содержание Binary Input N 260

Страница 1: ...or dimmer shutter or on off sending value switching at leading edge or at leading and trailing edge switching short long key depression sending value at leading edge or at leading and trailing edge duration of long key depression can be set used type of contacts can be set 11 S4 BinVal 240A01 4 binary inputs each input allows to send values at leading edge and or at leading and trailing edge allow...

Страница 2: ...mm flexible conductor with terminal pin crimped on gas tight 0 5 1 5 mm flexible conductor with connector sleeve 1 0 and 1 5 mm plain flexible conductor V WARNING When looping through the shared N conductor connection blocks 3 and 6 take care that the maximum connection current of 2 A as governed by the maximum permissible printed conductor load is not exceeded bus line pressure contacts on data r...

Страница 3: ...es Figure 2 Slide the device B1 onto the DIN rail B2 and swivel back the device until the slide clicks into place audibly Dismounting DIN rail devices Figure 2 Remove all connected wires press down the slide C3 with a screw driver and swivel the device C1 from the DIN rail C2 B1 C1 C2 C3 B2 Figure 2 Mounting and dismounting a DIN rail device Connecting input circuits Figure 3 The load circuits are...

Страница 4: ...am Dimensions in mm b 90 44 55 45 b 2 SU 1 Spacer unit SU 18mm Notes Technical Manual N 260 4 pages Siemens AG Automation and Drives Group Update http www siemens de installationstechnik Siemens AG 2001 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 7 1 3 4 ...

Отзывы: